Specifications - Haier MRV5-H Service Manual

Table of Contents

Advertisement

PART 2 Enginnering Data

12. Specifications

230V VRF Outdoor Unit
Items
Marketing Model Name
System
Combination
Model Name
Brand
Norminal Capacity (Btu/h)
Factory Model Number
Voltage, Cycle, Phase V/Hz/-
Electrical
Maximum Fuse Size A
Minimum Circuit Amp A
Rated Cooling Capacity@95°F (Btu/h)
EER @95 °F
IEER
Rated Heating Capacity @47°F(Btu/h)
COP @ 47°F
Rated Heating Capacity@17°F(Btu/h)
Performance
Non-Ducted
COP @ 17°F
SCHE
(115°F) Cooling Capacity(Btu/h)
Heating Capacity @5° (-15C)
Heating Capacity @-4°F (-20C)
Heating Capacity @-13°F (-25C)
Heating capacity @-22°F (-30C)
Rated Cooling Capacity@95°F (Btu/h)
EER @95 °F
IEER
Rated Heating Capacity @47°F(Btu/h)
COP @ 47°F
Rated Heating Capacity@17°F(Btu/h)
Performance
Ducted
COP @ 17°F
SCHE
(115°F) Cooling Capacity(Btu/h)
Heating Capacity @5°F
Heating Capacity @-4°F
Heating Capacity @-13°F
Heating capacity @-22°F (-30C)
New Heat Pump & Heat Recovery
MVHQ072ME2CA
MVHQ096ME2CA
6T
/
Haier
72000
AV08CMVURAB
AV10CMVURAB
208-230/60/3
208-230/60/3
40
30
69000
12.6
23.6
77000
3.5
53000
2.4
24.4
≥80% of rated
≥80% of rated
≥80% of rated
≥80% of rated
≥70% of rated
≥70% of rated
≥60% of rated
≥60% of rated
≥25% of rated
≥25% of rated
69000
12
20.5
77000
3.5
53000
2.4
20
≥80% of rated
≥80% of rated
≥80% of rated
≥80% of rated
≥70% of rated
≥70% of rated
≥60% of rated
≥60% of rated
≥25% of rated
≥25% of rated
165
MVHQ120ME2CA
8T
10T
/
/
Haier
Haier
96000
120000
AV12CMVURAB
208-230/60/3
50
60
38
41
91000
115000
11.9
11.6
23.1
23
103000
129000
3.5
3.5
72000
84000
2.4
2.5
23
21.7
≥80% of rated
≥80% of rated
≥70% of rated
≥60% of rated
≥25% of rated
91000
115000
12.2
11.2
21.8
21.6
103000
129000
3.5
3.5
72000
84000
2.4
2.5
21.4
21.4
≥80% of rated
≥80% of rated
≥70% of rated
≥60% of rated
≥25% of rated