Transfer Switch Terminal - Generac Power Systems GR-210 Operation And Maintenance Manual

Liquid-cooled diesel engine generator set
Table of Contents

Advertisement

CAUTION: Although you can operate single-
phase loads through the terminal lugs as well as
the receptacles, DO NOT attempt to connect any
3-phase loads to the receptacles.
• Wiring cables for connecting loads to terminal studs
must be rated 480 volts at 300 AC amperes (or
greater) for loads on E1, E2, E3, N and 240 volts at
700 AC amps (or greater) for loads on L1, L2 L3.
• When connecting electrical loads, be sure the volt-
age adjust dial is positioned to the correct voltage.
The dial permits you to adjust the voltage from
120/208 volts and 240/416 volts up to 139/240
volts and 277/480 volts.
CAUTION! Voltage adjust dial affects all recepta-
cles and terminals at the same time.
All receptacles and terminals are available at all
times and can be loaded at the same time. MAXI-
MUM TOTAL LOAD must not exceed generator rat-
ing.
Maximum load for single-phase or three-
phase operation must not exceed the rating for
that particular mode of operation (rating for sin-
gle-phase may be less than for three-phase opera-
tion).
The total load connected to any phase,
including loads connected to receptacles, must
not exceed the rated generator output per phase.
• Set voltage adjust dial to "120/208V" for 120 volts,
single-phase or 208 volts, 3-phase when connecting
for one of these voltages. See "Voltage Adjust Dial"
on page 12. Connect cord set leads as follows:
L1 to N = 120 volt, single-phase
L1 to L2 = 208 volt, 3-phase
L2 to N = 120 volt, single-phase
L2 to L3 = 208 volt, 3-phase
L3 to N = 120 volt, single-phase
L3 to L1 = 208 volt, 3-phase
• Set the voltage adjust dial to "139/240V" for 139
volt, single-phase or 240 volt, 3-phase when con-
necting for one of these voltages. See "Voltage Adjust
Dial" on page 12.Then connect cord set leads as
follows:
L1 to N = 139 volt, single-phase
L1 to L2 = 240 volt, 3-phase
L2 to N = 139 volt, single-phase
L2 to L3 = 240 volt, 3-phase
L3 to N = 139 volt, single-phase
L3 to L1 = 240 volt, 3-phase
WARNING! With voltage set line-to-line for 240V,
line-to-neutral voltage will be 139V at
receptacles.
NOTE:
General Information
GR-210 Generator Set
• Set the voltage adjust dial to "240/416V" for 240
volt, single-phase or 416 volt 3-phase when con-
necting for one of these voltages. See "Voltage Adjust
Dial" on page 12.Then connect cord set leads as
follows:
E1 to N = 240 volt, single-phase
E1 to E2 = 416 volt, 3-phase
E2 to N = 240 volt, single-phase
E2 to E3 = 416 volt, 3-phase
E3 to N = 240 volt, single-phase
E3 to E1 = 416 volt, 3-phase
• Set the voltage adjust switch to "277/480V" for 277
volt, single-phase or 480 volt, 3-phase when con-
necting for one of these voltages. See "Voltage Adjust
Dial" on page 12.Then connect cord set leads as
follows:
E1 to N = 277 volt, single-phase
E1 to E2 = 480 volt, 3-phase
E2 to N = 277 volt, single-phase
E2 to E3 = 480 volt, 3-phase
E3 to N = 277 volt, single-phase
E3 to E1 = 480 volt, 3-phase
CAUTION: Do NOT connect E1 or E2 or E3 to L1
or L2 or L3. Damage to equipment, personal
injury or death may result.
DANGER: Connect cable leads to the power ter-
minal studs only when the engine is shut down.
The panel door is equipped with a push-button
safety interlock switch (Figure 9) that prevents
engine startup and operation while the door is
open. Opening the door while engine is run-
ning immediately shuts down the engine. The
switch is provided for your protection. Do not
attempt to bypass or disconnect it.

TRANSFER SWITCH TERMINAL

The AC power panel includes a terminal strip for con-
necting an automatic transfer switch, such as a GTS
transfer switch (Figure 10). This connection allows the
use of the unit as a standby generator in practical appli-
cations or in emergency situations.
Figure 9 - Interlock Switch on Panel Door
Generac
Power Systems, Inc.
®
9