R3G310-PV69-02
6.1.1 Warning codes
Number of pulses
Motor status - LED
orange
1
Current limitation in
action
2
Line impedance too
high (DC-link voltage
unstable)
3
Power limiter in action
4
Output stage
temperature high
5
Motor temperature high
6
Temperature inside
electronics high
7
DC-link voltage low
8
Braking mode: set in
case of external drive
in opposite direction
at high speed for
lengthy period
9
Calibration of rotor
position sensor in
progress
10
Actual speed is lower
than run monitoring
speed limit
11
Open circuit at analog
input or PWM input
for the set value
13
DC-link voltage high
15
Line voltage high
16
Shake-loose function
activated
6.1.2 Status codes
Manual reset by "Switch off line voltage - wait briefly - switch line
voltage back on" or, if provided,
via the "Fan enable/disable" input
Number of
Motor status -
pulses
LED red
1
Phase failure or
line undervoltage
3
Output stage
overheating
4
Communication
error between
master
controller and
slave controller
6
Motor
overheating
Item no. 57702-5-9970 · ENU · Change 218409 · Approved 2020-09-18 · Page 16 / 18
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com
Operating instructions
Message at status
relay
Yes
Yes
Yes
Possible cause Possible
remedy
Missing phase
Check line
Poor power
voltage
supply quality
Electronics
Provide better
housing
cooling.
contaminated
Manual reset
required
External
Switch off line
supply applied
voltage
via Vout for
- wait -
setting
switch back on
parameters.
Internal error
Ambient
Reduce
temperature too
ambient
high
temperature
Impermissible
Correct
operating point
operating point.
Manual reset
required
7
Hall sensor error Internal error
8
Motor blocked
9
Speed limit
exceeded
11
Rotor position
sensor
calibration error
13
DC-link
undervoltage

6.2 Vibration testing

Checking of fan for mechanical vibration based on ISO 14694.
Recommendation: Every 6 months. Max. vibration severity is 3.5 mm/
s, measured at the motor fastening diameter on the motor support plate in
the direction of the motor axis of rotation and perpendicular to this.
Fig. 5: Example illustrating vibration measurement. The arrangement of
the sensors depends on the device concerned and the installation
situation.

6.3 Cleaning

To ensure a long service life, check the fans regularly for proper
operation and soiling. The frequency of checking is to be adapted
accordingly depending on the degree of soiling.
DANGER
Risk of injury from rotating fan.
→ Only clean when not in motion. Do not disconnect the fan
from the power supply, just switch it off via the control input.
This will prevent start-up of the fan.
; Dirt deposits on the motor housing can cause overheating of the motor.
Switch off line
voltage
- wait -
switch back on
Mechanical
Switch off
blockage
- check safe
isolation from
supply -
check
freedom of
movement of
rotor
-
-
Observe
Rotor position
ebm-papst
sensor
replacement
calibration
instructions
necessary.
Notify ebm-
papst
Line voltage not
Check the line
OK
voltage applied.

Advertisement

Table of Contents
loading