Download Print this page

Chromalox RADH-207 Installation Instructions Manual page 4

Electric radiant heaters

Advertisement

Wiring
ELECTRIC SHOCK HAZARD. Disconnect all
power before installing or servicing heater.
Failure to do so could result in personal injury
or property damage. Heater must be installed
by a qualified person in accordance with the
National Electrical Code, NFPA 70.
ELECTRIC SHOCK HAZARD. Any installation
involving electric heaters must be performed
by a qualified person and must be effective-
ly grounded in accordance with the National
Electrical Code to eliminate shock hazard.
1. Electrical connection to the Radiant Heater is made
through two openings tapped for 1/2" connec-
tor. Openings are in the top of the extruded heater
housing, one near each end.
2. Wiring should be run in flexible or rigid metal con-
duit and must be installed in accordance with the
requirements of the National Electrical Code and
such other local requirements as may be applica-
ble. NOTE: High temperatures will oxidize copper.
Do not use copper wire in connecting this heater.
Stranded, insulated, nickel-plated copper wire is
recommended.
3. Access to Radiant Heater terminals is obtained by
removing the two screws in each of the terminal box
covers.
4. A sufficient length of this wire (not Jess than 12")
should be used to extend from each heater terminal
into a connection box location where the tempera-
ture does not exceed 300°F.
5. Leave generous loop in wire when connecting to al-
low for expansion of heating element.
6. Assemble terminal, nut and wire as shown in Fig. 5.
Figure 5
7. Tighten the terminal nut securely with a wrench.
NOTE: Where circuit wiring is installed in locations
of high ambient temperature, conductors should be
insulated in accordance with requirements for tem-
perature and voltage.
8. SINGLE END WIRING may be made through one
of the wiring entries by bringing a lead through it
from the opposite end of the heating element us-
ing the wire-way provided behind integral reflector
in the housing extrusion. Wire used in making such
connections must be able to operate in high ambi-
ent and have a sufficiently high voltage rating for the
specific application. The maximum wire diameter is
limited by the wire-way and must not exceed .224"
over the insulation.
9. DELTA CONNECTIONS - When heaters occur in
multiples of three, they may be connected to, and
balanced across, three-phase lines. The most com-
monly used connection is the delta connection il-
lustrated in Figure 6.
A
B
C
D
E
3 Conductors
in 1 Conduit
Three phase Delta connections to minimize inductive
effect in conduits are made per this diagram. The rule:
run all 3 three-phase conductors in the same conduit
as far as possible. For single-phase, run only two con-
ductors and follow the same rule.
4
3 Conductors
in 1 Conduit
Radiant
F
Heaters
L1
L2
L3
Figure 6

Advertisement

loading

This manual is also suitable for:

Radh-310Radh-418Radh-525Radh-630Radh-736