3.3 Programming mode

This section describes the HART Commands used in the
device.
3.3.1 Universal Commands
The Universal Commands are the minimum command
set for all HART devices and provide access to information
useful in normal device operation.
Table 2 shows the supported Universal Commands for
this device.
0
Read Unique Identifier
1
Read Primary Variable
2
Read Loop Current and Percent Range
3
Read Dynamic Variables and Loop Current
6
Write Polling Address
7
Read Loop Configuration
8
Read Dynamic Variable Classifications
9
Read Device Variables with Status
11
Read Unique Identifier Associated with Tag
12
Read Message
13
Read Tag, Descriptor, Date
14
Read Primary Variable Transducer Information
15
Read Device Information
16
Read Final Assembly Number
17
Write Tag, Descriptor, Date
18
Write Tag, Descriptor, Date
19
Write Final Assembly Number
20
Read Long Tag
21
Read Unique Identifier Associated with Long Tag
22
Write Long Tag
38
Reset Configuration Changed Flag
48
Read Additional Device Status
3.3.2 Common Practice Commands
The Common Practice Commands are an optional
command set for HART devices. Table 3 shows the
supported Common Practice Commands for this device.
33
Read Unique Identifier
34
Read Primary Variable
35
Read Loop Current and Percent Range
42
Read Dynamic Variables and Loop Current
44
Write Polling Address
47
Read Loop Configuration
50
Read Dynamic Variable Classifications
51
Read Device Variables with Status
54
Read Unique Identifier Associated with Tag
59
Read Message
78
Read Tag, Descriptor, Date
79
Read Primary Variable Transducer Information
90
Read Real-Time Clock
103
Write Burst Period
104
Write Burst Trigger
105
Read Burst Mode Configuration
106
Flush Delayed Response Buffers
107
Write Burst Device Variables
108
Write Burst Mode Command Number
109
Burst Mode Control
115
Read Event Notification Bit Mask
116
Write Event Notification Bit Mark
117
Write Event Notification Timing
118
Event Notification Control
119
Acknowledge Event Notification
3.3.3 Device Specific Commands
The Device Specific Commands are commands unique
to this device only. These commands are included in the
Device Description (DD). Download the latest DD* at
www.ueonline.com to ensure optimum communication
between HART devices, gateway and host system. Table 4
shows the supported Device Specific Commands for this
device.
* The downloaded files should be placed in a folder
named with the manufacturer ID number and then a
child folder created using the device type number. The
folder should then be copied to the directory where DD
files are stored. New DD files simply replace the old and
work with all revisions of the same device.
128
Read Calibration Point
129
Write Calibration Point
131
Read Sensor Activation State
132
Read Base Unit Configuration String
133
Read Sensor Module Configuration String
Table 2
138
Read Sensor Type String
3.3.4 HART Command 128 Read
Calibration Point
Request bytes:
Bytes
Format
None
Response bytes:
Bytes
Format
0-3
Float
Command Specific Response Code:
Bytes
Format
0
Success
13
Description
Description
Concentration of gas used during
calibration
Description
No command specific errors
IM_TCD50 12
Table 3
Table 4
Table 5