Dometic RML 10.4 Installation Manual page 16

Absorber refrigerator
Hide thumbs Also See for RML 10.4:
Table of Contents

Advertisement

Available languages

Available languages

Installing the refrigerator
• The distance between the refrigerator and the rear wall must be at least 15 mm
but no more than 25 mm.
• A distance of more than 25 mm between the refrigerator and rear wall leads to
poor performance and increases the power consumption of the refrigerator.
Reduce the space behind the refrigerator to create adequate air inlet and outlet
ventilation (fig. 4, page 4). Use a ventilation plate, for example, to do this.
• If the minimum distance between the air inlet and outlet vents cannot be met, a
roof vent must be installed instead of the air outlet vent.
– The roof vent should be installed directly above the back of the refrigerator as
far as this is possible. Use an air duct (fig. 5 1, page 5) if you need to install
the roof vent offset; otherwise, heat will accumulate there.
– The distance between the air inlet vent and the roof vent must be at least
1350 mm (fig. 5, page 5).
– If a roof air conditioner is provided, the distance between the roof vent
(fig. 6 1, page 5) and the air outlet of the roof air conditioner (fig. 6 2,
page 5) must be at least 300 mm.
• The refrigerator must not be installed at the side of the air inlet and outlet vents as
this leads to poor performance and increases the power consumption of the
refrigerator.
• The air inlet and outlet vents must not be covered by vehicle parts (such as an
open door or by installing accessories such as bicycle racks) while operating.
• Install the refrigerator so that it is protected from excessive heat, as this leads to
poor performance and increases the power consumption of the refrigerator.
• The refrigerator must be installed in a draft-proof location.
16
RML10.4, RML10.4S, RML10.4T
EN