SMC Networks VP542-X536 Series Instruction Manual

Residual pressure relief valve with direct monitoring for use in safety related systems
Hide thumbs Also See for VP542-X536 Series:

Advertisement

Quick Links

VP500-TF2Z495EN-A
ORIGINAL INSTRUCTIONS
Instruction Manual
Residual pressure relief valve with direct
monitoring for use in safety related systems
(25A-)VP542/544(R)-X536(-##)
(25A-)VP544(R)-X538(-##)
25A-VP544(R)-X544
(25A-)VP544(R)-X555(-##)
VP544R-X575
(25A-)VP544(R)-X585(-##)
VP542R-X562
VP544R-X563
VP544R-X577
VP544(R)-X594
VP544(R)-X596
VP544-X597
VP542R-X615
VP542-X617
(25A-)VP742/744(R)-X536(-##)
(25A-)VP744(R)-X538(-##)
25A-VP744(R)-X544
(25A-)VP744(R)-X555(-##)
VP744(R)-X557
VP742R-X562
VP744R-X563
(25A-)VP744(R)-X585(-##)
VP744(R)-X596
VP744-X597
"###" and "##" represent numerical digits.
Note)
Safety component as defined by the Machinery
Directive 2006/42/EC article 2c/ The Supply of
Machinery (safety) Regulations 2008 part 2.4(2)(c)
The intended use of this valve is to vent a protected system to
atmosphere when it is de-energised. When properly integrated into a
suitable safety system the duplex valves are compatible for use in
systems up to Category 4, and the single valves are compatible for use
in systems up to Category 2 as defined by EN ISO 13849-1.
1 Safety Instructions
These safety instructions are intended to prevent hazardous situations
and/or equipment damage. These instructions indicate the level of
potential hazard with the labels of "Caution," "Warning" or "Danger."
They are all important notes for safety and must be followed in addition
*1)
to International Standards (ISO/IEC)
, and other safety regulations.
*1)
ISO 4414: Pneumatic fluid power - General rules and safety requirements
for systems and their components
ISO 4413: Hydraulic fluid power - General rules and safety requirements
for systems and their components
IEC 60204-1: Safety of machinery - Electrical equipment of machines.
Part 1: General requirements
ISO 10218-1: Robots and robotic devices - Safety requirements for
industrial robots - Part 1: Robots
• Refer to product catalogue, Operation Manual and Handling
Precautions for SMC Products for additional information.
• Keep this manual in a safe place for future reference.
1 Safety Instructions - continued
Danger indicates a hazard with a high level of risk which, if
Danger
not avoided, will result in death or serious injury.
Warning indicates a hazard with a medium level of risk
Warning
which, if not avoided, could result in death or serious injury.
Caution indicates a hazard with a low level of risk which, if
Caution
not avoided, could result in minor or moderate injury.
Warning
• Always ensure compliance with relevant safety laws and
standards.
• All work must be carried out in a safe manner by a qualified person in
compliance with applicable national regulations.
Caution
• The product is provided for use in manufacturing industries only. This
product must not be used in residential
areas.
2 Specifications
Warning
• Special specification products "-X###" and "-##", other than standard
'-X536/8 and X555, might have specifications different from those
shown in this Instruction Manual.
• Refer to individual drawings for special specifications.
2.1 Functional description
This product consists of either a single or dual channel valve
configuration connected to a main air supply, optionally via an integrated
soft-start valve. The valves are capable of performing the safety function
described in this document. The soft start valve is intended to allow the
end user to perform machine operational start up procedures with
reduced flow potential until a high operational pressure is achieved. At a
defined pressure the soft start valve applies full flow in order to achieve
full operation. The soft start function is intended for machine operation
purposes and not for the performance of a safety function.
2.2 Valve specifications
Standard
High pressure
Model
VP500
VP700
VP500
Type of Actuation
Normally closed
Return method
Spring return
Fluid
Air
Proof pressure [MPa]
1.05
1.5
Internal pilot operating pressure range [MPa]
0.25 to 0.7
0.25 to 1
External pilot operating
Main pressure
0.25 to 0.7
0.25 to 1
pressure range [MPa]
Pilot pressure
Same as main pressure
Ambient and operating fluid temperature [°C]
-10~+50 (no freezing / no condensation)
Ambient humidity
20 to 90% RH (no condensation)
Response time
See 2.12.2
Duty cycle
Contact SMC
Note 1)
Min. operating frequency
1 cycle per week
Max. operating frequency
30 cycles per minute
Lubrication
Note 2)
Not required
Note 3)
Note 4, 5)
Impact / Vibration resistance [m/s²]
150 / 30 m/s²
5 μm filtration or smaller
Air quality
Environment
Indoor use only
Enclosure (based on IEC60529)
IP65
Note 6)
B
[cycles]
10,000,000 cycles
5,000,000 cycles
10D
Maximum 20 years
Maximum 20 years
or when the
or when the number
Mission time [years of cycles]
number of cycles =
of cycles = B
whichever occurs
B
, whichever
10D
first.
Note 7)
Note 7)
occurs first.
VP#42-X536
350
590
-
VP#44-X536
480
810
-
Weight (examples) [g]
VP#44-X538
960
1560
-
VP#44-X555
1340
2220
-
VP#44-X585
-
-
1340
Table 1.
Note 1) The valve must be energised/de-energised at least once per week.
Note 2) If lubrication is used in the system, use class 1 turbine oil (no additive), ISO
VG32.
Note 3) See section 2.5 for switch impact/vibration specifications.
Note 4) Impact resistance:
• No malfunction resulted from the impact test using a drop impact tester.
• The test was performed in both energised and de-energised states to on
the axis of and at right angles to the direction of the main valve and
armature. (Values quoted are for a new valve).
2 Specifications - continued
Note 5) Vibration resistance:
• No malfunction occurred in a one-sweep test between 8.3 and 2000 Hz.
• Test was performed in both energised and de-energised states to the
axis of and at right angles to the direction of the main valve and armature
(Values quoted are for a new valve).
Note 6) The B
figure is estimated from SMC life tests under SMC test conditions.
10D
Note 7) See section 2.12.4 for details.
2.3 Flow specifications
Single channel
Single channel
VP542-X536
VP544-X536
Flow
1→2
2→3
1→2
2→3
Passage:
specifications
(P→A)
(A→R)
(P→A)
(A→R)
C[liter/(s.bar)]
8.9
8.9
8.8
8.8
b
0.16
0.20
0.07
0.13
Cv
2.2
2.1
2.0
2.0
Table 2.
Dual channel
Dual channel
VP544-X538
VP744-X538
Flow
1→2
2→3
1→2
2→3
Passage:
specifications
(P→A)
(A→R)
(P→A)
(A→R)
C[liter/(s.bar)]
6.5
6.7
10.3
9.7
b
0.08
0.10
0.08
0.08
Cv
1.3
1.3
2.3
2.1
Table 3.
Note 1) The air supply flow is from port 1 to port 2. The ports on the valve are clearly
identified with the corresponding numbers.
Note 2) For flow during soft start mode, see section 2.8.2.
Dual channel
Dual channel
VP544-X555/X585
VP744-X555/X585
Passage:
Flow
1→2
2→3
1→2
2→3
specifications
(P→A)
(A→R)
(P→A)
(A→R)
C[liter/(s.bar)]
5.2
6.7
9.8
9.7
b
0.06
0.10
0.08
0.08
Cv
1.1
1.3
2.1
2.1
Table 4.
2.4 Pilot valve specifications
Electrical entry
D or Y type DIN terminal (See 3.8.1)
VP700
Coil rated voltage [VDC]
Allowable voltage fluctuation
Power consumption [W]
Surge voltage suppressor
Indicator light
Table 5.
Note 1) Valve state is not defined if electrical input is outside of specified operating
ranges.
2.5 Limit switch specifications
Omron
G1/2 connector
Electrical entry
M12 connector
Contact resistance [mΩ]
25 max
5 VDC 1mA
Minimum permissible load
(resistive load)
Rated voltage [VDC]
Note 6)
Maximum permitted load current
[mA]
Maximum permitted load
,
10D
inductance [H]
Rated insulation voltage [V]
300
-
Electric shock protection class
Class II (EN60947-5-1)
-
Pollution degree
Level 3 (EN60947-5-1)
-
Vibration / Impact resistance
-
Table 6.
2220
Note 1) For the purposes of EN ISO 13849-2 table D.2 the switch is de-rated from
the figures specified by the switch manufacturer. The switch load must be
limited in the application in order to maintain the specified safety
performance, including the B
and mission time.
10D
Note 2) The Omron switch is subject to the following vibration and impact limitations
specified by the manufacturer:
• 'Contact opening time should be less than a 1 ms pulse under vibration
of 0.75 mm single amplitude, 10 to 55 Hz, 10 cycles in each direction for
45 minutes.'
• Impact: 300 m/s
2
(Contact open time: 1 ms maximum pulse)
2 Specifications - continued
Note 3) The Rockwell Automation switch is subject to the following vibration and
impact limitations specified by the manufacturer:
• Impact: IEC60068-2-7 (30gn (300m/s
• Vibration: IEC60068-2-6 (10...55Hz, 0.35mm amplitude).
2.6 Safety specifications
• Safety function: When the valve is de-energised the protected circuit is
vented to atmosphere.
• The single valve is compatible for use in systems up to Category 2
according to the Safety Standard when integrated into a suitable safety
Single channel
Single channel
system.
VP742-X536
VP744-X536
• The duplex valve assembly is compatible for use in systems up to
1→2
2→3
1→2
2→3
Category 4 according to the Safety Standard when integrated into a
(P→A)
(A→R)
(P→A)
(A→R)
suitable safety system.
15.1
15.3
14.7
15.0
• In this section, 'the Safety Standard' refers to EN ISO 13849-1 and 'the
0.21
0.22
0.05
0.17
Validation Safety Standard' refers to EN ISO 13849-2 as referenced in
3.6
3.7
3.3
3.4
the Declaration of Conformity.
• Information about compatibility with the Safety Standard is given in
section 2.12.
2.7 Pneumatic symbols (examples)
2.7.1 VP#42#-X536
Internal pilot
Operational mode, for soft start
Figure 1. Omron switch variant
mode see section 2.8
2.7.2 VP#44#-X538
24
Note 1)
-10% to +10%
0.45 per solenoid
Varistor
LED
Rockwell Automation
M12 connector
50 max
5 VDC 5mA
Internal pilot
(resistive load)
Figure 2. Omron switch variant
24
2.7.3 VP#44-X555/585
Note 1)
50
Note 1)
0.5
600
2), 3)
See note
Figure 3. Internal pilot, Rockwell switch variant
2
)), 3 pulses per axis).
External pilot
External pilot
Page 1 of 5

Advertisement

loading

Summary of Contents for SMC Networks VP542-X536 Series

  • Page 1 VP500-TF2Z495EN-A 1 Safety Instructions - continued 2 Specifications - continued 2 Specifications - continued ORIGINAL INSTRUCTIONS Danger indicates a hazard with a high level of risk which, if Note 5) Vibration resistance: Note 3) The Rockwell Automation switch is subject to the following vibration and Danger •...
  • Page 2 VP500-TF2Z495EN-A 2 Specifications - continued 2 Specifications - continued 2 Specifications - continued 2 Specifications - continued 2.10 Base mounted valve identification VP#44 valves are marked with mounting arrows, which are designed to point towards a mating arrow on the sub plate. 2.11 Batch code The batch code indicated in the product label translates to construction year / month according to the following table (eg.
  • Page 3: Installation

    VP500-TF2Z495EN-A 2 Specifications - continued 3 Installation - continued 3 Installation - continued 3 Installation - continued • Do not mount in a location exposed to radiant heat that would result in • Use clean air. If the compressed air supply includes chemicals, 2.12.3 Relationship of flow and response performance to safety 3.7 Noise temperatures in excess of the product’s specifications.
  • Page 4: How To Order

    VP500-TF2Z495EN-A 3 Installation - continued 3 Installation - continued 3 Installation - continued 6 Maintenance - continued • Make sure that the socket connector is tightened securely. Otherwise, 6.2 Replacement parts the rated degree of protection may not be maintained and vibration Gland nut Warning t: 0.5 mm...
  • Page 5: Limitations Of Use

    VP500-TF2Z495EN-A 7 Limitations of Use 7 Limitations of Use - continued • In order to meet a required performance level as defined by the Danger appropriate safety standard, the user must provide all the other • The machine designer is responsible for ensuring that the operation of necessary components to complete function of the safety system.

This manual is also suitable for:

Vp544-x536 seriesVp542r-x536 seriesVp544r-x536 seriesVp544-x538 seriesVp544r-x538 seriesVp544-x555 series ... Show all