Mounting; Observing Preconditions - OBO Bettermann UG 46-GS Mounting Instructions

Up flush-mounted boxes
Table of Contents

Advertisement

Mounting

6
6 1
14 | EN
Mounting

Observing preconditions

Maintaining installation zones
To prevent damage to cables, e.g. through drilling, cables routed in
a concealed manner according to DIN 18015-3:2016-09 may only be
routed vertically or horizontally and, if possible, only in the pre-specified
installation zones.
Spacings and installation zones according to DIN 18015-3:2016-09
10
Fig 4: Installation zones, dimensions in cm
Horizontal installation zones, maximum width 30 cm
Upper installation zone
Middle installation zone (for work
surfaces in kitchens and work-
shops)
Lower installation zone
Vertical installation zones, maximum width 20 cm
Windows and doors
Corners and edges
Fig 5: Installation zones
Installation height, devices and switches
Centre of sockets
Centre of switches
Centre of thermostats
Fig 6: Installation heights
– Maintain spacings and installation zones according to DIN 18015-
3:2016-09.
20
15
20
15
15
10
15 cm from ceiling
100 cm from floor
15 cm from floor
10 cm at the side from raw structure edge
10 cm at the side from raw structure edge
30 cm from floor
105 cm from floor
140 cm from floor
OBO Bettermann

Advertisement