P-1605 Return Pipe Replacement
Instructions- CX
Warning
This replacement kit shall be installed by a qualified service agent in accordance with these
instructions and all applicable codes and requirements of the authority having jurisdiction. If the
information in these instructions is not followed exactly a fire, an explosion or production of
carbon monoxide may result causing property damage, personal injury or loss of life.
The qualified service agency is responsible for the proper installation of this kit. The installation
is not proper and complete until the operation is checked as specified in these instructions.
Part #
251-201
When to Install the P-1605 Return Pipe Replacement Kit
Install the P-1605 kit if you need to replace the return pipe due to damage.
Note
A ladder or step may be required to have a clear vertical view of the work area.
Do not attempt to remove the assemblies without a clear view, as damage to the connectors,
screws or refractory may occur.
Replacement of CX Return Pipe
Preparing the Unit for Servicing
1. Remove call(s) for heat.
2. Remove power to the unit at a wall switch or a breaker.
3. Shut off gas supply to the boiler.
4. Allow the boiler to cool down.
5. Remove the front cover.
6. Drain the boiler. Open the supply pipe's manual air vent to break vacuum.
IBC Technologies Inc.
-
120-518E0
October 10, 2023
Return Pipe - CX
Description
Return Water Pipe Assembly
- Released Document
Quantity
1
|
1-844-432-8422
www.ibcboiler.com
1 of 2