Placement Guidelines

For placement, we recommend the guidelines required for RESET Air certification, which
requires RESET Air Accredited Monitors to be installed according to the following
requirements:
A. Wall-mounted and centrally-located within monitored spaces.
B. Mounted in the breathing zone: between 3 6 feet 0.9 1.8 meters) from the ground
(after finished floor to underside of the finished ceiling)*.
C. Located at least 16 feet (~5 meters) away from operable windows. In areas where
this is not possible, monitors must be located no closer to windows than half the
width of the space, measured linearly from the windows inwards.
D. Located at least 16 feet (~5 meters) away from air filters and diusers. In areas
where this is not possible, monitors must be located closer to air returns than air
diusers.
E. Hard-wired to a permanent power source (recommended but not mandatory).
*Note: this aligns with ASHRAE 62.1
Kaiterra Square Air Quality Monitor Deployment Guide