INSTRUCTION MANUAL
2-WIRE POSITION TRANSMITTER
(flameproof, rotary motion type)
BEFORE USE ....
Thank you for choosing us. Before use, please check con-
tents of the package you received as outlined below.
If you have any problems or questions with the product,
please contact our sales office or representatives.
■ PACKAGE INCLUDES:
VOS-ER unit ........................................................................(1)
Lever assembly
Lever ........................................................................(1)
Connecting pin ........................................................(1)
Nailed nut ................................................................(1)
Nut ...........................................................................(1)
Screws for attaching the lever (M5 × 8) .............................(1)
Plain washer (M5) ...............................................................(1)
Toothed washer (M5, external teeth) .................................(1)
Toothed washer (M5, internal teeth) ..................................(1)
Link set ................................................................................(1)
(Provided only when ordered as an option)
Note: Bracket and other components necessary to attach the
VOS-ER to actuator are to be provided by the customer.
■ MODEL NO.
Confirm Model No. marking on the product to be exactly
what you ordered.
WARNING
Explosions could result in death or serious injury:
• The enclosure cover must be completely closed to meet
explosion-proof/flameproof requirements.
• Do not open the cover in explosive atmospheres when the
circuit is alive.
• Before opening the enclosure, wait at least for 60 seconds
after the power is removed.
• Before you connect or disconnect the wiring, turn off the
power supply for safety. Do not connect or disconnect
unless the area is known to be non-explosive.
• Whenever you need to measure voltage across the
terminals, make sure that there is no danger of explosion
in the atmosphere.
• Verify the certification of the product described on the
specification label on the product.
• Verify that the operating atmosphere of the product is
consistent with the appropriate hazardous locations
certifications.
• Verify that the environmental temperature is within the
temperature class required for the area.
Failure to follow these installation guidelines could result
in death or serious injury:
• Make sure only qualified personnel perform the instal-
lation.
MG CO., LTD. www.mgco.jp
5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
MODEL
SAFETY FEATURES & CAUTIONS
Failure to follow the following wiring and installation
guidelines could result in death or serious injury:
■ FLAMEPROOF APPROVAL
• Ex d IIB T5
• TIIS TC14314
• Ambient temperature -5 to +40°C
■ WIRING
• Follow wiring practice according to the local code.
• Make sure that diameter of the applicable cable is correct.
• Electrical wiring into the flameproof enclosure is done by
cable system. Be sure to use the cable gland attached to
the product.
• Be sure to close all unused cable entry conduits with the
stopping plug attached to the product.
• Before turning the power supply on, be sure to close the
enclosure cover tightly.
• Be sure to earth the unit.
• For external earthing or bonding connection a cable lug
shall be used so that the conductor is secured against
loosening and twisting and that contact pressure is
maintained.
POINTS OF CAUTION
■ GENERAL
• Cut power supply to the unit before wiring to it.
• Torque applied to the screws attaching the cover is 2.5 –
3.5 N·m.
■ ENVIRONMENT
• Inside building. If outside, keep away from direct sunlight.
• Operating temperature -5 to +50°C (23 to 122°F)
Limited to -5 to +40°C (23 to 104°F) for use in an
explosive atmosphere.
• Do not place the unit in a strong magnetic field.
■ ACTUATOR SIDE LEVER
• When the actuator side lever is provided by the customer,
be sure that the diameter of the hole threading the con-
necting pin is 5 millimeters or wider.
Diameter of connecting pin: 5
VOS-ER
0
mm
–0.03
EM-4764 Rev.9 P. 1 / 5

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the VOS-ER and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for MG VOS-ER

  • Page 1 Note: Bracket and other components necessary to attach the • For external earthing or bonding connection a cable lug VOS-ER to actuator are to be provided by the customer. shall be used so that the conductor is secured against loosening and twisting and that contact pressure is ■...
  • Page 2: Component Identification

    Connecting Pin ■ CONNECTING THE VOS-ER SIDE LEVER TO THE VOS-ER UNIT Nailed Nut Connect the lever to the VOS-ER unit with a screw included Factory Lever, VOS Side in the package, with a plain washer and a toothed washer Assembled.
  • Page 3: Electrical Connections

    VOS-ER ■ CONNECTING THE VOS-ER SIDE LEVER TO THE ACTU- ATOR SIDE LEVER (with optional Link Set by us) Connect between the levers utilizing the nailed nut as in Figure 3. Lever, Actuator Side Factory Assembled. (Can not be Bolt disassembled.)
  • Page 4: Adjustment Procedure

    A – B and C – D is the same. See Figure 5. 3) Then attach the VOS-ER so that the length A – C and B – D is also the same (The square A – B – C – D must be a Fig.
  • Page 5: Maintenance

    Be sure to return the • If the VOS-ER is installed outside the building or where gasket (sealing ring) to the proper position. it is subject to water or metallic dust particles, check that there is no crack or bruise on its gasket (sealing ring).

Table of Contents