Weil-McLain CGi 4 Series Manual page 58

Gas-fired water boilers
Hide thumbs Also See for CGi 4 Series:
Table of Contents

Advertisement

CGi
SERIES 4 — GAS-FIRED WATER BOILER —
11c
Troubleshooting — control module lights
Electrical shock hazard — Wherever you see ▲ TURN OFF POWER ▲, follow the instructions. Failure to
follow instructions could result in severe personal injury, death or substantial property damage.
Are main manual shutoff valve and gas valve open?
No
• ▲
▲ to boiler at service switch or breaker.
TURN OFF POWER
• Open main manual shutoff valve and boiler gas valve (per
Operating instructions in this manual). Wait at least 45 seconds.
• Turn on power at service switch or breaker. Allow boiler to cycle .
Does FLAME light flash now?
No
• Verify inlet gas pressure at gas
• Boiler should be in
normal operating
sequence.
• Observe operation
until thermostat is
satisfied and blower
has completed its
post-purge cycle.
• ▲ TURN OFF POWER ▲
to boiler at service switch
or breaker.
• Remove burner shield (see
Figure 40, item 4, page 64
for location.
• Verify pilot gas line is not
kinked, obstructed or
damaged and is correctly
attached to pilot and gas
valve.
• Verify pilot ignition electrode,
electrode ceramic and spark
lead wire from control are in
good condition. Spark gap
should be approximately 1/8".
• Correct any above problems,
replacing pilot if burner or
wiring is damaged.
• Reinstall burner shield to
operate boiler for retest after
any changes or corrections.
• If none of the above corrects
problems, then replace the
control module and retest.
58
CHART 6 –– FLAME light flashing and Power light on steady
Also –– Troubleshooting failure to establish main flame.
Yes
Yes
valve:
Natural gas – 5.0" w.c. min/14.0"
w.c. max
Propane – 11.0" w.c. min/14.0"
w.c. max
Is gas present at gas valve inlet and
within above range?
Yes
No
• Contact gas supplier to correct
pressure or gas supply.
• ▲ TURN OFF POWER ▲
to boiler at service switch or
breaker.
• Remove burner shield (see
Figure 40, item 4, page 64
for location.
• Verify pilot burner is securely
attached to pilot bracket, bracket
is securely attached to cross tie,
and there is no corrosion on
the parts which would affect the
ground path for flame sense.
• Verify that pilot flame rod, flame
rod ceramic and lead wire from
control module to flame rod are in
good condition.
• Correct any above problems,
replacing pilot if burner or wiring
is damaged.
Boiler Manual
• Is pilot flame visible through inspection port ?
No
• Check the voltage across
terminals PV and C of
the gas valve.
Is 24VAC present there?
Yes
• If the wiring from the
control module to gas
valve is intact, replace the
control module.
• Retest.
• Verify inlet gas pressure at gas valve:
Natural gas – 5.0" w.c. min/14.0" w.c. max
Propane – 11.0" w.c. min/14.0" w.c. max
Is gas present at gas valve inlet and within above range?
No
• ▲ TURN OFF POWER ▲
• Check flame signal – Detach sense lead from ignition control
(Figure 38, Item 8, page 52).
• Connect negative lead of MICROAMMETER to control sense
terminal (Figure 38, Item 8, page 52). Connect positive
lead of MICROAMMETER to sense wire.
• DISCONNECT red wire connected to terminal MV of the gas
valve.
• Turn on power to boiler and allow to cycle. As soon as pilot
is burning, the MICROAMMETER should read at least 1.0
microamp.
Is flame signal at least 1.0 microamp ?
No
• If none of the previous steps
(including replacing pilot)
corrects problem, then replace
the control module, reinstall
burner shield and retest.
(cont.)
Yes
• Make sure ground wire
terminal is securely fastened
to control module mounting
screw.
No
• Check the voltage across
terminals of MV and C
of the gas valve.
Is 24VAC present there?
No
Yes
to boiler at service switch or breaker.
Yes
• If the wiring from the
control module to gas
valve is intact, replace the
control module and retest.
Part Number 550-142-302/0124
Yes

Advertisement

Table of Contents
loading