PLC DATA ACCESS

The following list identifies the data points inside PLC that can be monitored by SCADA system.
An Ethernet connection is configured with factory default IP address of 192.168.0.10. Follow
PLC user manual to adjust IP address to suit installation. Configuration of SCADA should not
allow access to any other PLC address than those listed below.
PLC Address Data type
%R1100
Integer
%R1101
Integer
%R1102
Integer
%R1103
Integer
%R1104
Integer
%R1105
Integer
%R1106
Integer
%R1107
Integer
%R1108.1
Binary
%R1108.2
Binary
%R1108.3
Binary
%R1108.4
Binary
%R1108.5
Binary
%R1108.6
Binary
%R1108.7
Binary
%R1108.8
Binary
%R1108.9
Binary
%R1108.10
Binary
%R1108.11
Binary
%R1108.12
Binary
%R1108.13
Binary
%R1108.14
Binary
%R1108.15
Binary
%R1108.16
Binary
NG-SR IOM
Description
Cooler Outlet Temperature
Heater Outlet Temperature
Heater Sheath Temperature
Heat Termination Temp.
Heating Time
Cooling Time
Spare
Dewpoint Analyzer
Blower Mtr. Overload Alarm
Heater Sheath Overtemp Alarm
Cooler Mtr. Overload Alarm
Cooler Outlet Temp High Alarm
Heater Outlet Temp High Alarm
Thermocouple Open Alarm
Dewpoint High Alarm
Heater Chamber Alarm
Spare
Spare
Spare
Spare
Regeneration Running
Heating Done
Regeneration Done
Dryer Power On
38
Value Range
-346 to 2100°F
-346 to 2100°F
-346 to 2100°F
-346 to 2100°F
0-600 minutes
0-600 minutes
-148 to 68°F
ON=Alarm
ON=Alarm
ON=Alarm
ON=Alarm
ON=Alarm
ON=Alarm
ON=Alarm
ON=Alarm
ON=Running
ON=Heating Done
ON=Regen Done
ON=Power On