IF FOR ANY REASON THIS EQUIPMENT IS NOT ENTERED INTO SERVICE BEFORE 30 DAYS
FROM DATE OF SHIPMENT, THE ELECTRICAL CONTROL ENCLOSURE(S) MUST BE
PROTECTED FROM HAZARDS OF DAMP ATMOSPHERE WHEN STORED EITHER INDOORS
OR OUTDOORS.
MINIMUM PROTECTION WOULD REQUIRE CHANGING DESICCANT BAGS, PLUGGING ALL
OPENINGS AND SEALING ALL ELECTRICAL CONTROL ENCLOSURES WITH WATERPROOF
MATERIAL OR PURGING WITH DRY INSTRUMENT AIR.
1. PURGE THE SYSTEM TO REMOVE OXYGEN (CONTAINED IN AIR) PRIOR TO STARTUP.
2. MAKE SURE ALL BLOCK VALVES TO GAUGES ARE OPEN BEFORE ACCURATELY
READING PRESSURE GAUGES.
3. DO NOT OPEN ANY PORT UNTIL SYSTEM HAS BEEN FULLY DEPRESSURIZED.
4. DO NOT OPEN HIGH VOLTAGE PANEL WITH AREA KNOWN TO HAVE HAZARDOUS
GAS PRESENT.
5. LOOSEN HEATER SUPPORT BOLTING BEFORE REGENERATING UNIT.
6. BURN POTENTIAL HAZARD EXISTS. WEAR PROTECTIVE CLOTHING WHEN WORKING
IN AND AROUND UNIT.
NG-SR-IOM January 2007
CAUTION
IMPORTANT STORAGE INSTRUCTIONS
SAFETY NOTICE - DANGER
2