Item
2
3
4
5
6
7
8
9
10
11
NG-SR IOM
Object
Description
Cool time
Regeneration cool time can be adjusted to handle
numeric entry
temperature issues that may occur at cooldown.
Touching screen where value is shown opens
keypad to enable setpoint change. Entry is limited to
maximum of 600 minutes
Heater control
Regeneration heater output can be changed using
temperature
this parameter. Touching screen where value is
numeric entry
shown opens keypad to enable setpoint change.
Entry is limited to maximum of 450°F and a
minimum of 0°F.
Heat
Regeneration heat termination temperature can be
termination
changed using this parameter. Touching screen
temperature
where value is shown opens keypad to enable
numeric entry
setpoint change. Entry is limited to maximum of
350°F and a minimum of 100°F.
High dewpoint
Outlet moisture alarm can be changed using this
temperature
parameter. Touching screen where value is shown
numeric entry
opens keypad to enable setpoint change. Entry is
limited to maximum of -40°F and a minimum of
-100°F.
Heater sheath
Regeneration heater protection limit can be adjusted
temperature
to simulate alarm. Touching screen where value is
numeric entry
shown opens keypad to enable setpoint change.
Entry is limited to maximum of 800°F.
Heater outlet
Regeneration heater max. output can be adjusted to
temperature
simulate alarm. Touching screen where value is
numeric entry
shown opens keypad to enable setpoint change.
Entry is limited to maximum of 500°F.
Cooler OFF
Regeneration cooler OFF can be changed to
temperature
prevent freeze up in low ambient temperatures.
numeric entry
Touching screen where value is shown opens
keypad to enable setpoint change. Entry is limited to
maximum of 75°F and a minimum of 40°F.
Maximum
Compressor run time is setpoint is used to trigger
compressor
regeneration message. Touching screen where
run time
value is shown opens keypad to enable setpoint
numeric entry
change. Entry is limited to maximum of 150 hours.
Compressor
Compressor run time can be enabled or disabled
run time
using this button. Pushbutton toggles operation of
enable
feature.
pushbutton
Alarms
When pressed, main alarm screen showing current
pushbutton
status becomes visible. If flashing, then an alarm is
active.
15
PSB INDUSTRIES