CAMDEN CX-PS150UL Installation Instructions

Electrified locks, relays and timers

Advertisement

Quick Links

Electrified Locks, Relays and Timers
CX-PS150UL
POWER SUPPLY / CHARGER FOR ACCESS CONTROL
AND EGRESS DOORS
INSTALLATION INSTRUCTIONS
THIS PACKAGE INCLUDES
1 - Holding Screw
2 - 2K2 Resistors
1 - Instruction manual
1. GENERAL DESCRIPTION
The CX-PS150UL is a power supply and charger that delivers a consistent
supply of 1.7 amps (1 amp for locking devices, 500mA for battery charging
and 200 mA for devices that need to stay powered regardless of the Fire
Alarm status) at a nominal voltage of either 12VDC or 24VDC. It features
two output terminals, one output is intended for maglock while the other is
intended for a strike, and is safeguarded against over current by a 2.5 amp
P.T.C. This power supply unit is designed to accommodate a 1 - 4Ah battery.
It is UL listed, adhering to the 7th Edition of UL294 standards, and also
meets the requirements of ULC-S533.
2. SPECIFICATIONS
Input
Output
Auxiliary Output
Dimensions
3. KEY FEATURES
Incorporates a built-in 500 mA battery charger for sealed lead acid or
gel cell batteries.
Features battery reversal protection to safeguard against potential
damage.
Designed for automatic switch over to stand-by battery in the event of
AC power failure.
Equipped with LED indicators on the enclosure door for easy power
source monitoring: green LED for AC power, blue LED for DC power.
UL294 PERFORMANCE LEVEL
Destructive Attack
Line Security
Endurance Level
Standby Power
1 - Strain Relief Connector
1 - Camden Programming Harness
60Hz 1.8A max,120VAC for CX-PS150UL
1 Amp continuous @ 12/24VDC
200mA @ 12/24VDC
8-7/16"W x 9-5/16"H x 3-9/16"D
(214 mm x 236 mm x 91 mm)
Level I
Level I
Level IV
Level IV
4. BATTERY STAND-BY SPECIFICATION
Output:
Stand-by 4 hr
12VDC /4AHBattery
24VDC /4AHBattery
5. DIMENSIONS
8"
[203mm]
3 1/4"
3 1/4"
[83mm]
[83mm]
4"
[101mm]
3 13/16"
[97mm]
3 3/8"
3 3/8"
[85mm]
[85mm]
C L
NOTE:
This power supply should be installed in compliance with the National
Electric Code (NFPA 70) CSAC22.1, Canadian Electric Code, Part 1 and all
applicable Local Codes. Installation to be performed by qualified technical
personnel.
Alarm 5 min
1A
500mA
1A
500mA
3 9/16"
[91mm]
8 7/16"
[214mm]
L C
9 5/16"
[236mm]
Page 1 of 4

Advertisement

loading

Summary of Contents for CAMDEN CX-PS150UL

  • Page 1 1 - Camden Programming Harness 1 - Instruction manual 1. GENERAL DESCRIPTION 4. BATTERY STAND-BY SPECIFICATION The CX-PS150UL is a power supply and charger that delivers a consistent Output: Stand-by 4 hr Alarm 5 min supply of 1.7 amps (1 amp for locking devices, 500mA for battery charging...
  • Page 2 5. Fire Alarm / Access Control Interface Connection: The Normally Open (NO), Normally Closed (NC) input from the Fire Alarm Control Panel (FACP) or Access Control Panel (ACP) can trigger the CX-PS150UL series operation. Connect the NO or NC from the FACP or ACP output to the FIRE/ ACP TRIGGER terminals.
  • Page 3 CX-PS150UL Power Supply INSTALLATION INSTRUCTIONS 7. CONNECTION For JL Jumper and Camden Programming Harness Camden Programming Harness Page 3 of 4...
  • Page 4 3) Mains Fail (Manual Reset). Using the provided Camden Set Switch tool, place the connector end over the two pins marked as JL. Press the switch 3X (0.5 second per press). The outputs now will not restore when the AC Mains are restored. It will need a manual reset to restore the outputs.