SH-003 - Smoke / Heat Detector High Temp Kit Installation Instructions
5 Configuration
Provisioning a SIM100 while connected to the SH-003 Kit requires an initial setup. This setup can be
completed using either a Maretron gateway paired with a PC running Maretron's N2KAnalyzer
application or by using any of the Maretron DSM Series displays. The same programming features
are available using either of the methods illustrated above. The SIM100 offers 6 isolated channels for
monitoring Open, Closed, or Error status behavior of a connected device. When programming a
single channel of the SIM100, you will apply a 'Name' to the circuit connection and illustrate whether
the End-of-Line (EOL) Resistor is connected within that circuit.
The EOL Resistor is an 8KΩ resistor that is positioned near the load/device that is being monitored
across the two connections. If this feature is enabled for the individual channel, the SIM100 provides
a 'sample' voltage to the channel in order to validate the integrity of the circuit up to the load/EOL
Resistor.
The SIM100 module will broadcast an NMEA 2000
channel. The NMEA 2000
broadcast according to the SIM100's Instance and Channel number. In addition to the status report
for each channel, the SIM100 with report both a Switch Counter (PGN 130836) and a Switch Timer
(PGN 130837) parameter. This will provide the user with additional information for each connected
device to take into account how many times the status switched state and the duration in state.

6 Equipment Testing

To test an SH-003 system connected to a SIM100, the NMEA 2000 network for SIM100 and the
SH-003 detector will need to be powered. After power-up, the respective NMEA 2000
Indication should indicate 'Off' (Normal State). If either detector power or any connection to SIM100 is
lost for the channel, the respective NMEA 2000
(Maintenance Required). If a detector is in an Alarm State, the respective NMEA 2000
Indication should indicate 'On' (Alarm State). Perform additional testing and maintenance routine as
outlined in the provided 'Apollo Orbis Marine Multi-Sensor Detector Instructions'.

7 Technical Support

For installation support, please contact:
Page
6
®
message broadcast for each SIM100 channel 'Switch Status Indication' is
Maretron, a Littelfuse Brand
120 Intracoastal Pointe Dr.
Jupiter, FL 33477 USA
http://www.maretron.com
E-mail:
support@maretron.com
Toll-Free: (866) 550-9100
Phone: (602) 861-1707
®
Switch Status Indication (PGN 127501) for that
®
Switch Status Indication should indicate 'Error'
®