Download Print this page

Choosing A Mounting Location - Maretron SH-003 Installation Instructions Manual

Smoke / heat detector - high temp kit

Advertisement

SH-003 - Smoke / Heat Detector High Temp Kit Installation Instructions
1 Overview
The SH-003 kit can be used for general smoke / heat detection; however, it is ideal for use in high
temperature areas such as engine rooms. The SH-003 kit contains a Smoke/Heat Detector, a
Sounder, and an Auxiliary Relay that will interface into a single channel of a Maretron SIM100.
1.1 Unpacking the Box
The SH-003 Kit is comprised of 3 components and 2 mounting bases.
Each component provides its original manufacture's installation instructions and guidelines.
* Please retain these documents to provide full equipment specifications and troubleshooting.
• Apollo ORB-OH-43001-MAR Optical/Heat Multi-sensor Detector with Base ORB-MB-00001
• Klaxon PSS-0039 Sounder Module with Base ORB-RB-40004-MAR
• Cranford Controls RIU-R24 Auxiliary Relay
• 8KΩ EOL (End of Line) Resistor for circuit supervision
1.2 Temperature Operating Range
The supported temperature range for the SH-003 Kit is -13°F to 158°F (-25°C to 70°C)
1.3 Electrical Operating Range
For the complete installation of the SH-003 Kit, requires 24V DC source supply.
• Apollo ORB-OH-43001-MAR Optical/Heat Detector
• Klaxon PSS-0039 Sounder Module
• Cranford Controls RIU-R24 Auxiliary Relay

2 Choosing a Mounting Location

Please use the following steps as a guide for installation of the SH-003 Kit.
Install SH-003 Kit in accordance with ABYC and NFPA guidelines for fire and smoke
1)
detection based on your application.
Never exceed 900 sq. ft. of area for any single detector's range.
2)
Detector and sounder can be ceiling or wall mounted directly or fastened to various sizes of
3)
standard electrical boxes.
Pre-Mount and wire the detector and sounder bases before installing the head units. Twist
4)
head units (detector unit and sounder unit) onto respective bases in a clockwise motion. To
remove, twist head in a counterclockwise motion. Both detector and sounder heads are
keyed to the base.
5)
Wire SH-003 in accordance with ABYC or NEC guidelines to select correct wire size
(22-16 AWG) and any other applicable wiring guidelines based on your application type.
The application of dielectric grease on the detector and sounder base connections is
6)
recommended.
Do not mix high current harnessing with fire detection harnessing. For the best wiring
7)
choice, choose a marine grade, tinned copper, 16 AWG twisted pair cable.
The detector comes with a pre-installed dust cover. Maintain cover affixed to detector
8)
throughout vessel construction or until first use.
Page
4
( 5-33V DC)
( 9-60V DC)
(18-40V DC)
Revision 1.3

Advertisement