6.3.3 Changing the actual air flow ........31 Air quality ..............12 6.3.4 Changing the air distribution profile ....... 31 Capacity test ............12 6.3.5 Professor XP pressure / airflow diagram ....31 4. Connections ..............13 Water flow rate ............31 Water connections ..........13 6.4.1 Pre-setting of valves ..........
See also the separate document “Accessories." Lindab will also provide you with a full ventilation system, with a wide range of Lindab Safe components. See also “Air 14-60 Duct Systems." kg ! 2.2 Safe operation...
Please remember to remove plastic folio and other protection material before commissioning and clean the product before hand over. Lindab reserves the right to make changes without prior notice 2021-05-19...
| fo r a b e t te r c l i ma te Installation instruction Professor XP 2.10 Packing, unpacking guideline Never use water pipe connections for lifting F-60 I-60 14-60 kg ! Lindab reserves the right to make changes without prior notice 2021-05-19...
The product is factory pre-set with the customer-demanded primary air flow rate and static pressure loss settings. The label both records and guarantees the settings with personal signature of the responsible Lindab employee. Lindab reserves the right to make changes without prior notice...
0802 0806 1202 1206 * As a plus feature the Professor XP I-62, J-60, K-60, L-60, X-60, Y-60 and Z-60 models can be ordered as well. See 3.2 for more details. 2.13 Order code examples Order : xx-xxxxx Pos : 1.4 m...
Two types of connection covers are available for Professor XP F-45 and XP F-60. Regula Multi connect card For details and ordering, go to 5.5.1 in this document. Go to Regula for details. Lindab reserves the right to make changes without prior notice 2021-05-19...
3.1 Product description The Professor XP is a 2-way active chilled beam and can be standardly prepared for ventilation and cooling (2-pipe connection) or cooling and heating (4-pipe connection). It is both available in an integrable I-45/I-60 and an exposed version F-45/F-60.
Page 10
Example: Professor XP-I-62-B1-1202-1.4 A (L J-60, K-60, L-60, X-60 with flanges Professor XP-L-60-A1-1202-1.4 Examples: A (L A (L Professor XP-J-60-A1-1202-1.4 = Nominal length ( Order length ). Lindab reserves the right to make changes without prior notice 2021-05-19...
11.8 Minimal cooling or minimal heating 2-pipe 11.5 Table 3. Professor XP, weight and water volume for I60 / F60 with different battery types. Possible battery configurations for Professor XP models Professor XP F-60 and I-60: All battery types possible.
3.9 Capacity test Lindabs active chilled beams are Eurovent-certified and tested according to EN-15116. Please visit Professor XP on www.lindQST.com and see Eurovent for more details. Lindab reserves the right to make changes without prior notice 2021-05-19...
When connecting a panel or a beam with the piping system either a push-on fitting or a compression coupling should be used. Lindab have tested and recommends John Guest push on fittings as well as push-on fittings from Tectite (available as accessory.
• Please refer to the suppliers manual. = 70 mm (to ensure you can open the couplings again). Lindab flexible hoses are available with straight end (male) for direct connection to Lindab valves also. Lindab reserves the right to make changes without prior notice...
4.1.5 Possible connections water cooling or heating (2-pipe, standard) All the Professor XP active chilled beams can have either a “2-pipe water connection” or a "4-pipe water connection" as standard (see 4.1.6). The 2-pipe water connection beam contains one water circuit only (cooling or heating).
The 4-pipe water connection beam contains two water circuits. One for heating and one for cooling. The dimension for all water pipe connections are Ø = 12 mm. Professor XP: F-45, F-60, I-45 and I-60 cooling or heating (standard), I-62, J-60, K-60, L-60, X-60, Y-60 and Z-60 (ceiling adapted models).
Front view of XP-X model. * NB! 157.5* All dimensions marked (*) are valid and the same for all ceiling adapted models. Go to 5.2.2 to see dimensions for all ceiling adapted models. Lindab reserves the right to make changes without prior notice 2021-05-19...
Installation instruction Professor XP 4.2 Air connections 4.2.1 Air connection installation The primary air supply must be connected with instructions from a ventilation specialist. Lindab’s chilled beams can beneficially be used together with Lindab’s Safe duct systems. ® We recommend a flexible duct connection, like Lindab DRATMFU-100, to balance out different installation heights or directions between connection and duct and avoid sound will be diverted from piping system to the ceiling.
Heating link - S Cooling link - S Supply link - N Supply link - L Supply in - N Supply in 24V - L LINDAB (with protection covers, optional). Lindab reserves the right to make changes without prior notice 2021-05-19...
Supply link - N Supply link - L Supply in - N Supply in - 24V - L NB: Wire colours LINDAB differ from standard NB: Wire colours differ from standard Lindab reserves the right to make changes without prior notice 2021-05-19...
See Regula Secura for more details. Condensation sensor and Regula Secura Regula Secura Cable to Regula Secura from sensor Inlet pipe Strip Condensation sensor Strip Battery Faceplate Lindab reserves the right to make changes without prior notice 2021-05-19...
( Plus feature ) T24/T15 Lay-in 625 ( I-62 ) Water T24/T15 Lay-in 675 ( I-67 ) Water Not cleanable Not cleanable ( Plus feature ) ( Plus feature ) 619x619 669x669 Lindab reserves the right to make changes without prior notice 2021-05-19...
** Flange dimension. - = Model has no flange, see also 5.4 : Ceiling systems overview, go to 5.2 ceiling systems. ( previous page ). Table 4. Dimensions of Professor XP ceiling adapted models. Lindab reserves the right to make changes without prior notice...
5.3.2 Exposed, sealed to the ceiling Professor F models 5.3.6 Recessed in suspended (permanent) ceiling 5.3.3 Exposed, free hanging Professor I models Professor F models and ceiling adapted models Lindab reserves the right to make changes without prior notice 2021-05-19...
= Nominal length ( Order length ). ** : Flange dimension. - = Model has no flange. : Ceiling systems overview, go to 5.2 ceiling systems. Table 5. Dimensions of Professor XP plus feature models. Lindab reserves the right to make changes without prior notice 2021-05-19...
3.6 meters faceplate completely before with a weight at aprox. installation in ceiling. 52 kg. Go to part 7. Maintenance, Use professional lifting 7.2 Open inlet faceplate. equipment. Lindab reserves the right to make changes without prior notice 2021-05-19...
Page 27
14-60 kg ! Heavy load ! Longest Professor XP models are 3.6 meters with a weight at aprox. 52 kg. Use professional lifting equipment. Lindab reserves the right to make changes without prior notice 2021-05-19...
Page 28
Professor XP 5.5.1 Connection covers for Professor XP-F models Two different types of connection covers are available for Professor XP F-45 and XP F-60. Type CC for covering between two beams and CW for covering from one beam to wall.
6.3.1 Measuring static nozzle pressure and air pressure • To measure the air pressure, a manometer, (analogue or digital) will be needed. Lindab recommends PC410. • Insert the measuring tube onto the specialized measuring nozzle.
225 250 275 300 325 350 375 [l/s] Example using diagram 1 (see 6.3.5) shows needed number of open nozzles to reach a desired air flow at a given pressure. Lindab reserves the right to make changes without prior notice 2021-05-19...
(planned) water flow rates (calculated with LindQST\waterborne calculator). Lindab refers to the proportional method, where all beams (panels or facade units) are balanced to the same proportion of the requested water flow rate. Lindab reserves the right to make changes without prior notice...
> 2.7 m The faceplate now hangs in sevice wire, it can be removed completely when demounted from service wire. Reverse shown steps E - A to reinstall faceplate Lindab reserves the right to make changes without prior notice 2021-05-19...
Page 33
> 2.7 m The faceplate now hangs in sevice wire, it can be Service wires removed completely when demounted from service wire. Reverse shown steps E - A to reinstall faceplate Lindab reserves the right to make changes without prior notice 2021-05-19...
Note that you have 2 inspection hatches if you have 2 x 100 ventilation air supply connections. One in each end. Access hatch Via access hatch gain access directly to duct and other connec- ted devices. 7.4 Lower battery Not relevant for Professor XP. Lindab reserves the right to make changes without prior notice 2021-05-19...
| fo r a b e t te r c l i ma te Installation instruction Professor XP 8. Accessories Ask Lindab for the accessories mentioned in this document. Additional accessories (or additional dimensions) are available on request.** Order code Order number...
Page 36
We at Lindab have therefore made it our most important objective to contribute to an indoor climate that improves people’s lives. We do this by developing energy-efficient ventilation solutions and durable building products.
Need help?
Do you have a question about the Professor XP and is the answer not in the manual?
Questions and answers