Once the appliance starts, it will run through the
following steps:
1. The water temperature drops below the set
temperature of (for example) 65°C. The electronic
controller detects a demand and starts the heating
cycle.
-
The icon
is activated.
-
The message HEAT DEMAND appears.
a
ON
Ê
13:45 Thursday
63ÉC
Tset 65ÉC
HEAT DEMAND
2. Once demand is registered, the fan is started to
exhaust any gases that may be present. This
phase is called pre-purge and lasts about 15
seconds.
-
The icon
is activated.
-
The message PRE PURGE appears.
a
ON
Ê Ê
13:45 Thursday
63ÉC
Tset 65ÉC
PRE PURGE
3. During the pre-purge, the pressure switch closes.
-
The icon
is activated.
-
The message PRESSURE SWITCH
appears.
a
ON
Ê Ê Ê
13:45 Thursday
63ÉC
Tset 65ÉC
PRESSURE SWITCH
4. After some time, the pre-purge ceases and the
electronic controller reduces the fan speed to the
ignition speed. This is followed by the (pre-)glow of
the hot surface igniter.
-
The icons
and
-
The icon
is activated.
a
ON
Ê
Ê
13:45 Thursday
63ÉC
Tset 65ÉC
GLOW PLUG
54
Starting and running
are dimmed
5. After a number of seconds pre-glow, the gas
control is opened and ignition takes place.
-
The icon
is activated.
-
The message IGNITION appears.
a
ON
Ê
Ê Ê
13:45 Thursday
63ÉC
Tset 65ÉC
IGNITION
6. After ignition, the flame is detected and the
appliance will be running. This means that actual
heating has started. The fan speed then increases
to the normal working speed, and the pressure
switch closes:
-
The icon
is dimmed.
-
The icons
and
-
The message RUNNING appears.
a
ON
Ê
Ê
Ê Ê
13:45 Thursday
63ÉC
Tset 65ÉC
RUNNING
7. When the water is up to temperature, the heat
demand drops off and the post-purge starts. This
lasts about 25 seconds.
-
The icons
,
and
-
The icon
is activated.
-
The message POST PURGE appears.
a
ON
Ê Ê
13:45 Thursday
65ÉC
Tset 65ÉC
POST PURGE
8. Following the post-purge, the fan stops and the
pressure switch opens:
-
The icons
and
-
The message POST PURGE vanishes.
a
ON
14:05 Thursday
65ÉC
With any subsequent heat demand, the heating cycle
will resume from step 1.