Instruction manual BFC
n
min
IMD-0423 R0
The display will now show INTERNAL CHECK for about 10 seconds and
go to the main menu.
INTERNAL CHECK
MENU
»OFF
^ ON
È WEEK PROGRAM
7. Activate the "ON mode" by going through the following steps:
-
Press the blue arrow once ( ) to position the cursor in front of ON and
press
. The display shown here will appear.
»START OPERATION
^ CHANGE SETPOINT
È
Tset=65ÉC
-
Confirm the
The appliance is now in the "ON mode" and will ignite.
8. Once the display shows the text RUNNING you must wait about 1 minute
before reading the dynamic pressures (the fan needs this time to run up to
full rotational speed).
9. Use the pressure gauge to read the supply pressure at 1nipple
(1)
(3.4.3 "Gas
data").
Note
Consult the mains gas supply company if the supply pressure is not correct.
10. Use the pressure gauge to read the burner pressure at nipple
(2)
(3.4.3 "Gas
data").
If the burner pressure is not correct and the appliance is fitted with a blank plate,
you will not be able to adjust the pressure. Finalise
this case, consult your installation engineer or supplier.
If the appliance is indeed fitted with a burner pressure regulator, the pressure
can be adjusted as described in the procedure
pressure").
0063
by pressing START OPERATION.
(3.11.4
(3.11.3 "Adjusting the
"Finalising"), and in
37