No.
Name
1
OT terminal
2
Ground cable
AC output power
3
cable
DC input power
4
cable
RS485
communications
cable (terminal
block)
5
RS485
communications
cable (RJ45
network port)
Solar tracker
6
power cable
(optional)
7
Cable tie
Model/
Specifications
M8
2
16 mm
outdoor copper
cable
2
35 mm
outdoor copper
cable
PV cable that meets the
1100 V standard
Computer cable
DJYP2VP2-22 2x2x1
Outdoor shielded
network cable/CAT 5E
Dual-layer three-core
outdoor copper cable
with a conductor cross-
sectional area of 10
mm
2
N/A
Description
When using outdoor copper cables for AC
connection, select copper wiring terminals.
For requirements on the cables and
terminals of other materials, see user
manual.
•
If you choose the ground point on the
enclosure for connecting a ground cable,
prepare the ground cable.
•
If you choose the ground point in the
maintenance compartment for
connecting a ground cable, use a four-
core AC output power cable and do not
have to prepare a ground cable.
If you choose the ground point in the
maintenance compartment for connecting a
ground cable, use a four-core cable. Under
other conditions, use a three-core cable.
N/A
•
If RS485 communication is used, prepare
the RS485 communications cable.
•
A terminal block is recommended for
connecting to the RS485 communications
cable.
N/A
N/A
6