After the wiring work has been completed, measure the insulation resistance, and make
sure that it reads at least 1 MΩ.
- Failure to do so may result in electric leakage, malfunction, or fire.

1-6. Precautions for relocating or repairing the unit

Only qualified personnel must relocate or repair the unit. Do not attempt to disassemble or
alter the unit.
- Failure to do so will result in refrigerant leakage, water leakage, serious injury, electric shock, or
fire.
Do not service the unit in the rain.
- Doing so may result in electric leakage, electric shock, wire shorting, malfunction, smoke, or fire.

1-7. Additional precautions

To reduce the risk of failures of the compressor or valves, follow the instructions below to
prevent abrasive components contained in sandpaper or cutting tools from entering the
refrigerant circuit.
- To deburr pipes, use a reamer or other deburring tools, not sandpaper or sanding tools that use
abrasive materials.
- To cut pipes, use a pipe cutter, not a grinder or other tools that use abrasive materials.
- When cutting or deburring pipes, do not allow cutting chips or other foreign matters to enter the
pipes.
- If cutting chips or other foreign matters entered pipes, wipe inside the pipes to remove them.
Do not turn off the power immediately after stopping operation.
- Wait for at least five minutes after the unit has stopped before turning off the power. Failure to do
so may result in drain water leakage or the mechanical failure of sensitive parts.
The unit must be periodically inspected by a dealer or qualified personnel.
- If dust or dirt accumulates inside the unit, the drain pipes may become clogged, and water
leakage from the pipes may wet the surroundings and generate odours.
Turn on the power at least 12 hours before starting operation. Keep the power turned on
throughout the operating season.
- Insufficient energizing will result in malfunction.
Do not use the air conditioner for special purposes (e.g. keeping food, animals, plants,
precision devices, or art objects in a room).
- Such items could be damaged or deteriorated.
Collect the refrigerant and properly dispose of it in accordance with local regulations.
Do not install the unit on or over items that are subject to water damage.
- When the room humidity exceeds 80% or if the drain pipe is clogged, condensation may collect
and drip from the indoor unit onto the ceiling or floor.
WT09973X01