9-3-2. Joint Pipe Kit
A Joint Pipe Kit is used to connect an indoor unit of P/M100 model or above.
(1) R2 system
Indoor unit model
P100 to P250/M100 to M140
* When connecting P100 through P250/M100 through M140 models of indoor units to two ports, set the dipswitch SW4-6 on the BC controller to
ON.
* When including only PEFY-P50/63/71/80/100VMHS2-E units, connect the two ports and set the dipswitches SW4-1 and SW4-6 on the BC
controller to ON.
* When connecting PEFY-P50/63/71/80/100VMHS2-E units to two ports, use a Joint Pipe Kit CMY-R160-J1.
* Although using a single port is possible, cooling performance will somewhat decrease. When connecting P/M100 through P/M140 models of
indoor units or PEFY-P50/63/71/80/100VMHS2-E units to a single port, set the dipswitches SW4-1 and SW4-6 to OFF.
(2) Hybrid City Multi system
・Connect the pipes on site, referring to the HBC controller Installation Manual.
・CMY-R160-J1 is used in an R2 system, and cannot be used in a Hybrid City Multi system.
9-3-3. Outdoor unit twinning kit
Outdoor unit twinning kit is used to combine multiple outdoor units.
Total capacity of outdoor units
(E)P400 to (E)P650YSNW
(E)P700 to (E)P1100YSNW

9-4. Pipe connection example

9-4-1. Example of pipe connection between outdoor units
・PURY-(E)P200YNW-A2/TR2 through PURY-(E)P500YNW-A2/TR2 can be used in a Hybrid City Multi system.
Contact your dealer when connecting the larger capacity units in a Hybrid City Multi system.
WT09973X01
Kit model
CMY-R160-J1
Kit model
CMY-R100VBK4
CMY-R200VBK4
On-site piping
Twinning Kit
The pipe section before the twinning pipe must
have at least 500 mm (19-11/16 in) of straight
section.
24