Mitsubishi Electric CITY MULTI PURY-P-YNW-A2 Installation Manual page 48

Air-conditioners for building application
Table of Contents

Advertisement

(2) When MA remote controllers are connected
* Move the power jumper from
CN41 to CN40. *
1
* SW5-1: ON *
2
* Leave the power jumper
connected to CN41.
* SW5-1: ON *
2
Shielded cable
Main remote controller
Sub remote controller
System controller
*1 When a power supply unit is not connected to the centralized control transmission cable, move the power jumper from CN41 to CN40 on
only one of the outdoor units.
*2 If a system controller is used, set SW5-1 on ALL of the outdoor units to ON.
*3 When a PAR-CT01MA, PAR-4XMAA, or PAR-3XMAA ("X" represents 0 or later) is connected to a group, no other MA remote controllers
can be connected to the same group.
*4 In an R2 system: BC, BS
In a Hybrid City Multi system: HB, HS
Maximum allowable length of control cables
Transmission cables via outdoor units
Transmission cables
Remote controller cables
*5 When extending the length of the transmission cables to 1000 m (3280 ft), consult your dealer.
WT09973X01
Group 1
OC
CN41 CN40
*4
BC
(51)
(52)
TB02
TB3
M1 M2 S
M1M2
M1 M2
M1M2 S
TB7
L
3
OC
CN41
*4
BC
(53)
(54)
TB02
TB3
M1 M2 S
M1M2
M1 M2 S
M1M2 S
TB7
A B
S
L
+ L
+ L
1
2
3
L
, L
+ L
, L
1
3
4
m
+ m
, m
1
2
47
L
1
Group 3
IC
IC
*4
BS
(01)
(04)
(55)
TB02
TB5
TB15
TB5
TB15
M1 M2 S
S
1 2
M1 M2 S
1 2
A B
MA
L
4
IC
IC
(03)
(02)
TB5
TB15
TB5
TB15
1 2
M1 M2 S
1 2
A B
MA
+ L
, L
+ L
+ L
≤ 500 m (1640 ft)
4
1
2
6
, L
+ L
≤ 200 m (656 ft)
6
2
6
+ m
+ m
+ m
≤ 200 m (656 ft)
1
2
3
4
Group 5
IC
IC
(05)
(06)
2
TB5
TB15
TB5
TB15
M1 M2 S
1 2
M1 M2 S
1 2
4
A B
A B
MA
MA
IC
(07)
TB5
TB15
M1 M2 S
1 2
*5