E-KC-100 SERIES HEAD MOUNTED TYPE
TEMPERATURE CONVERTER USER MANUAL
The E-KC-100 converter is designed for use in an industrial environment.
The package of the
cert f cate.
After open ng the package, please v sually check whether the type of the transm tter s su table
for the order, whether the above-ment oned parts are m ss ng and whether the transm tter has
been damaged dur ng sh pment.
Before nstall ng and operat ng the controller, please read the user manual thoroughly.
The nstallat on and conf gurat on of the controller must only be performed by a person qual f ed n nstrumentat on.
Keep the un t away from flamable gases, that could cause explot ons.
Do not use alcohol or other solvents to clean the transm tter. Use a clean cloth soaked n water t ghtly squeezed
to gently w pe the outer surface of the transm tter.
It s not used n med cal appl cat ons.
1. DESCRIPTION
E-KC-100 series transmitters are microprocessor based industrial
instruments in plastic case. E-KC-100 transmitters are used to
convert the thermocouple and resistance thermometer signals into
standard 4-20 mA The configuration of the transmitter is done by
PC, using a software programme supplied by Elimko.
The RS 232 connection hardware is also available from Elimko.
2. TECHNICAL SPECIFICATIONS
2.1. OPERATING RANGE and EASURING ACCURACY
(at 24 V supply voltage and 25°C ± 3°C ambient temperature)
LOWER
STANDARD
SENSOR
RTD
Pt-100
IEC 60751
-200°C
B
E
-200°C
J
-200°C
K
-200°C
IEC 60584
N
-200°C
T/C
R
S
T
-200°C
L
-200°C
DIN 43710
U
-200°C
mV
-2000mV
If the input type and scale is not specified while ordering, factory settings are;
Input Type
: Pt-100, and
Scale
: 0-200°C.
KY-KC100-0224-1
E-KC-100 converter
conta ns; the
M
UPPER
MINIMUM
LIMIT
LIMIT
SPAN
850°C
50°C
±0.25°C
100°C
1800°C
100°C
±2.00°C
840°C
50°C
±0.50°C
1120°C
50°C
±0.50°C
1360°C
50°C
±0.50°C
1300°C
50°C
±0.50°C
-40°C
1760°C
100°C
±1.00°C
-40°C
1760°C
100°C
±1.00°C
400°C
50°C
±0.50°C
900°C
50°C
±0.50°C
600°C
50°C
±0.50°C
500mV
25mV
±0.075mV
Converter
, user manual and guarantee
2.2. General Specifications
Ele
ctrical
Supply Voltage
Voltage Drop
Environmental Conditions:
Operating Temperature
Protection Class
Cal brat on Temp.
Mechan cal:
D mens ons
We ght (approx.)
Connect on Cables
Res stance Thermometer (RTD) / Res stance Input:
Sensor Connect on
Maximum Wire Resistance
Error Signaling
Thermocouple (TC) / mV Input:
Input Impedance
Maximum Wire Resistance
Cold Junction
Compensation (CJC)
Error S gnal ng
Output:
Output Signal
ACCURACY
Load Resistance
A/D
D/A
Operating Influences:
Ambient Temperature
CJC Error (For TC Inputs)
EMC Immunity
±0.1%
Span
Electromagnetic Compatibility:
The E-KC-100 meets the requirements of
TS EN 61326-1.
:
10.0 - 30 V DC
9.0 V
-10°C to +55°C
IP 00,
IP 66 (DIN 43729 mounted on
type B head)
25°C ±3°C
Ø 44.0 mm x 21.5 mm
40 g
Max. 1.5 mm² (AWG 16)
3-Wire
100
Wire Break (Output current
can be configured Up / Down.)
> 10 M
100
Constant, Internal NTC,
External Pt-100 (Configurable)
W re Break (Output current
can be conf gured Up / Down.)
4 - 20 mA or 20 - 4 mA
[V
-10]× 50
supply
(600
W
< ± 0.01% / °C
< ± 1.0 °C
< ± 0.5% Span
KY-KC100-0224-1
W
at 22 V DC)
Need help?
Do you have a question about the E-KC-100 Series and is the answer not in the manual?
Questions and answers