3.9

FAN SPEED CALIBRATION

Verification and calibration are necessary, in the case of transformation to other types of gas, in the extraordinary maintenance
phase with replacement of the PCB, air/gas circuit components or in the case of installations with flue extraction systems, with
horizontal concentric pipe measuring more than 1 metre.
The appliance's heat output is correlated to the length of the air intake and flue exhaust pipes.
This decreases with the increase of pipe length.
The appliance leaves the factory adjusted for minimum pipe length (1m coaxial).
- Activate flue test (Par. 3.15);
- Detect the flue signal ∆P (Ref. 12 and 13, Fig.53);
- Compare the signal ∆P and, if necessary, correct the S1 operating parameters with the following table:
Victrix Plus 24HY
G20 (x50 = RPM)
G31 (x50 = RPM)
∆P<170 Pa
S1 = 121
S1 = 115
∆P≥170 Pa
S1 = 123
S1 = 118
∆P≥220 Pa
S1 = 126
S1 = 121