Mitsubishi Electric CITY MULTI PUHY-P72-432TNU-A Data Book page 28

Table of Contents

Advertisement

1. SPECIFICATIONS
Outdoor Model
Indoor Model
Power source
Cooling capacity
(Nominal)
Power input
(460) Current input
(Rated)
Power input
(460) Current input
Temp. range of
Indoor
cooling
Outdoor
Heating capacity
(Nominal)
Power input
(460) Current input
(Rated)
Power input
(460) Current input
Temp. range of
Indoor
heating
*3 Outdoor
Indoor unit
Total capacity
connectable
Model/Quantity
Sound power level (measured in anechoic room) *4
Refrigerant
Liquid pipe
piping diameter
Gas pipe
Set Model
Model
Minimum Circuit Ampacity
Maximum Overcurrent Protection
FAN
Type x Quantity
Airflow rate
Control, Driving mechanism
Motor output
*5 External static press.
Compressor
Type x Quantity
Manufacture
Starting method
Motor output
Case heater
Lubricant
External finish
External dimension H x W x D
Protection
High pressure protection
devices
Inverter circuit (COMP./FAN)
Fan motor
Refrigerant
Type x original charge
Control
Net weight
Heat exchanger
HIC circuit (HIC: Heat Inter-Changer)
Pipe between unit and
Liquid pipe
distributor
Gas pipe
Defrosting method
Drawing
External
Wiring
Standard
Document
attachment
Accessory
Optional parts
Remarks
Notes:
1.Nominal cooling conditions (Test conditions are based on AHRI 1230)
Indoor: 80°FD.B./67°FW.B. (26.7°CD.B./19.4°CW.B.), Outdoor: 95°FD.B. (35°CD.B.)
2.Nominal heating conditions (Test conditions are based on AHRI 1230)
Indoor: 70°FD.B. (21.1°CD.B.), Outdoor: 47°FD.B./43°FW.B. (8.3°CD.B./6.1°CW.B.)
3.When applying product below -4°F, consult your design engineer for cold climate application best practices,
including the use of a backup source for heating.
4.Cooling mode/Heating mode
5.External static pressure option is available (0.12 in.WG, 0.24 in.WG, 0.32 in.WG/30 Pa, 60 Pa, 80 Pa).
* Due to continuing improvement, above specifications may be subject to change without notice.
MEES23K040
Non-Ducted
*1 BTU/h
kW
kW
A
BTU/h
kW
kW
A
W.B.
D.B.
*2 BTU/h
kW
kW
A
BTU/h
kW
kW
A
D.B.
W.B.
dB <A>
in. (mm)
in. (mm)
PUHY-P120YNU-A (-BS)
A
A
Propeller fan x 2
cfm
3
m
/min
L/s
Inverter-control, Brushless DC motor
kW
0.46+0.46
0 in.WG (0 Pa)
Inverter scroll hermetic compressor x 1
MITSUBISHI ELECTRIC
Inverter
kW
7.7 x 1
kW
MEL32
Pre-coated galvanized steel sheet (+powder coating for -BS
<MUNSELL 3Y 7.8/1.1 or similar>
in.
71-5/8 x 48-7/8 x 29-3/16
mm
1,818 x 1,240 x 740
High pressure sensor, High pressure switch at 4.15 MPa
(601 psi)
Over-current protection
R410A x 21 lbs + 9 oz (9.8 kg)
lbs (kg)
640 (290)
Salt-resistant cross fin & copper tube
Copper pipe, tube-in-tube structure
in. (mm)
1/2 (12.7) Brazed
in. (mm)
1-1/8 (28.58) Brazed
KE94G652
Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be
referred to the Installation Manual.
PUHY-P240YSNU-A (-BS)
3-phase 3-wire 460 V ±10% 60 Hz
240,000
70.3
19.97
27.8
228,000
66.8
18.61
25.9
59~75°F (15~24°C)
23~126°F (-5~52°C)
270,000
79.1
22.12
30.8
258,000
75.6
20.52
28.6
59~81°F (15~27°C)
-13~60°F (-25~15.5°C)
50~130% of outdoor unit capacity
P04~P96/2~50
83.5/84.5
5/8 (15.88) Brazed
1-1/8 (28.58) Brazed
25
40
7,750
220
3,670
-
Pre-coated galvanized steel sheet (+powder coating for -BS
type)
High pressure sensor, High pressure switch at 4.15 MPa
-
LEV and HIC circuit
Auto-defrost mode (Reversed refrigerant cycle)
KL94T779
Installation Manual
Details refer to External Drw
Outdoor Twinning kit: CMY-Y100CBK3
joint: CMY-Y102SS/102LS-G2,CMY-Y202S/302S-G2
Header: CMY-Y104/108/1010C-G
Y-Series
Ducted
18.26
25.4
20.41
28.4
PUHY-P120YNU-A (-BS)
25
40
Propeller fan x 2
7,750
220
3,670
Inverter-control, Brushless DC motor
0.46+0.46
0 in.WG (0 Pa)
Inverter scroll hermetic compressor x 1
MITSUBISHI ELECTRIC
Inverter
7.7 x 1
-
MEL32
type)
<MUNSELL 3Y 7.8/1.1 or similar>
71-5/8 x 48-7/8 x 29-3/16
1,818 x 1,240 x 740
(601 psi)
Over-current protection
-
R410A x 21 lbs + 9 oz (9.8 kg)
640 (290)
Salt-resistant cross fin & copper tube
Copper pipe, tube-in-tube structure
1/2 (12.7) Brazed
1-1/8 (28.58) Brazed
KE94G652
Unit converter
BTU/h
=kW x 3,412
3
cfm
=m
/min x 35.31
lbs
=kg/0.4536
*Above specification data is
subject to rounding variation.
25