1. SPECIFICATIONS
Outdoor Model
Indoor Model
Power source
Cooling capacity
(Nominal)
Power input
(208-230) Current input
(Rated)
Power input
(208-230) Current input
Temp. range of
Indoor
cooling
Outdoor
Heating capacity
(Nominal)
Power input
(208-230) Current input
(Rated)
Power input
(208-230) Current input
Temp. range of
Indoor
heating
*3 Outdoor
Indoor unit
Total capacity
connectable
Model/Quantity
Sound power level (measured in anechoic room) *4
Refrigerant
Liquid pipe
piping diameter
Gas pipe
Set Model
Model
Minimum Circuit Ampacity
Maximum Overcurrent Protection
FAN
Type x Quantity
Airflow rate
Control, Driving mechanism
Motor output
*5 External static press.
Compressor
Type x Quantity
Manufacture
Starting method
Motor output
Case heater
Lubricant
External finish
External dimension H x W x D
Protection
High pressure protection
devices
Inverter circuit (COMP./FAN)
Fan motor
Refrigerant
Type x original charge
Control
Net weight
Heat exchanger
HIC circuit (HIC: Heat Inter-Changer)
Pipe between unit and
Liquid pipe
distributor
Gas pipe
Defrosting method
Drawing
External
Wiring
Standard
Document
attachment
Accessory
Optional parts
Remarks
Notes:
1.Nominal cooling conditions (Test conditions are based on AHRI 1230)
Indoor: 80°FD.B./67°FW.B. (26.7°CD.B./19.4°CW.B.), Outdoor: 95°FD.B. (35°CD.B.)
2.Nominal heating conditions (Test conditions are based on AHRI 1230)
Indoor: 70°FD.B. (21.1°CD.B.), Outdoor: 47°FD.B./43°FW.B. (8.3°CD.B./6.1°CW.B.)
3.When applying product below -4°F, consult your design engineer for cold climate application best practices,
including the use of a backup source for heating.
4.Cooling mode/Heating mode
5.External static pressure option is available (0.12 in.WG, 0.24 in.WG, 0.32 in.WG/30 Pa, 60 Pa, 80 Pa).
* Due to continuing improvement, above specifications may be subject to change without notice.
MEES23K040
Non-Ducted
*1 BTU/h
kW
kW
A
BTU/h
kW
kW
A
67.0-60.6
W.B.
D.B.
*2 BTU/h
kW
kW
A
BTU/h
kW
kW
A
71.7-64.9
D.B.
W.B.
dB <A>
in. (mm)
in. (mm)
PUHY-P120TNU-A (-BS)
A
50-46
A
80-70
Propeller fan x 2
cfm
7,750
3
m
/min
220
L/s
3,670
Inverter-control, Brushless DC motor
kW
0.46+0.46
0 in.WG (0 Pa)
Inverter scroll hermetic compressor x 1 Inverter scroll hermetic compressor x 1 Inverter scroll hermetic compressor x 1
MITSUBISHI ELECTRIC
Inverter
kW
7.7 x 1
kW
-
MEL32
Pre-coated galvanized steel sheet
(+powder coating for -BS type)
<MUNSELL 3Y 7.8/1.1 or similar>
in.
71-5/8 x 48-7/8 x 29-3/16
mm
1,818 x 1,240 x 740
High pressure sensor, High pressure
switch at 4.15 MPa (601 psi)
Over-current protection
-
R410A x 21 lbs + 9 oz (9.8 kg)
lbs (kg)
605 (274)
Salt-resistant cross fin & copper tube
Copper pipe, tube-in-tube structure
in. (mm)
1/2 (12.7) Brazed
in. (mm)
1-1/8 (28.58) Brazed
KE94G655
Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be
referred to the Installation Manual.
PUHY-P288TSNU-A (-BS)
3-phase 3-wire 208-230 V ±10% 60 Hz
288,000
84.4
23.21
71.5-64.7
274,000
80.3
21.74
59~75°F (15~24°C)
23~126°F (-5~52°C)
323,000
94.7
25.23
77.8-70.3
308,000
90.3
23.27
59~81°F (15~27°C)
-13~60°F (-25~15.5°C)
50~130% of outdoor unit capacity
P04~P96/2~50
82.5/84.0
3/4 (19.05) Brazed
1-3/8 (34.93) Brazed
PUHY-P96TNU-A (-BS)
40-36
60-50
Propeller fan x 2
6,700
190
3,170
Inverter-control, Brushless DC motor
0.46+0.46
0 in.WG (0 Pa)
MITSUBISHI ELECTRIC
Inverter
5.5 x 1
-
MEL32
Pre-coated galvanized steel sheet
(+powder coating for -BS type)
<MUNSELL 3Y 7.8/1.1 or similar>
71-5/8 x 48-7/8 x 29-3/16
1,818 x 1,240 x 740
High pressure sensor, High pressure
switch at 4.15 MPa (601 psi)
Over-current protection
-
R410A x 21 lbs + 9 oz (9.8 kg)
LEV and HIC circuit
580 (263)
Salt-resistant cross fin & copper tube
Copper pipe, tube-in-tube structure
3/8 (9.52) Brazed
7/8 (22.2) Brazed
Auto-defrost mode (Reversed refrigerant cycle)
KL94T774
KE94G655
Installation Manual
Details refer to External Drw
Outdoor Twinning kit: CMY-Y300CBK2
joint: CMY-Y102SS/102LS-G2,CMY-Y202S/302S-G2
Header: CMY-Y104/108/1010C-G
Y-Series
Ducted
20.87
64.3-58.2
23.43
72.2-65.3
PUHY-P72TNU-A (-BS)
29-26
45-40
Propeller fan x 1
6,000
170
2,830
Inverter-control, Brushless DC motor
0.92
0 in.WG (0 Pa)
MITSUBISHI ELECTRIC
Inverter
3.8 x 1
-
MEL32
Pre-coated galvanized steel sheet
(+powder coating for -BS type)
<MUNSELL 3Y 7.8/1.1 or similar>
71-5/8 x 36-1/4 x 29-3/16
1,818 x 920 x 740
High pressure sensor, High pressure
switch at 4.15 MPa (601 psi)
Over-current protection
-
R410A x 14 lbs + 5 oz (6.5 kg)
470 (213)
Salt-resistant cross fin & copper tube
Copper pipe, tube-in-tube structure
3/8 (9.52) Brazed
7/8 (22.2) Brazed
KE94G672
Unit converter
BTU/h
=kW x 3,412
3
cfm
=m
/min x 35.31
lbs
=kg/0.4536
*Above specification data is
subject to rounding variation.
11