Items To Be Used; Package Contents; Commercially Available Items; Selecting An Installation Site - Mitsubishi Electric TRANE TCMBG-SJ11N4 Installation Manual

Air conditioners for building application
Table of Contents

Advertisement

Available languages

Available languages

2. Items to be used

2.1. Package contents

The table below lists all the items and their quantities included in the package.
TCMBG
TCMBM
0104SJ11N4
0108JA11N4
0106SJ11N4
1012JA11N4
0108SJ11N4
1016JA11N4
1012SJ11N4
1016SJ11N4
Item
Washer for
2 kinds
1
construction
(4 each)

3. Selecting an installation site

3.1. About the product

Warning:
Do not use refrigerant other than the type indicated in the manuals
provided with the unit and on the nameplate.
- Doing so may cause the unit or pipes to burst, or result in explosion or fire
during use, during repair, or at the time of disposal of the unit.
- It may also be in violation of applicable laws.
- MITSUBISHI ELECTRIC CORPORATION cannot be held responsible
for malfunctions or accidents resulting from the use of the wrong type of
refrigerant.
This unit uses R410A-type refrigerant.
Piping for systems using R410A may be different from that for systems using
conventional refrigerant because the design pressure in systems using
R410A is higher. Refer to the Data Book for more information.
Some of the tools and equipment used for installation with systems that use
other types of refrigerant cannot be used with the systems using R410A.
Refer to the Data Book for more information.
Do not use the existing piping, as it contains chlorine, which is found in
conventional refrigerating machine oil and refrigerant. This chlorine will
deteriorate the refrigerant machine oil in the new equipment. The existing
piping must not be used as the design pressure in systems using R410A
is higher than that in the systems using other types of refrigerant and the
existing pipes may burst.

3.2. Installation site

Install the unit in a place not exposed to rain. The BC controller is designed
to be installed indoors.
Install the unit with adequate space around it for servicing.
Do not install the unit in a place that would result in the piping length
restrictions being exceeded.
Install the unit in a place not exposed to direct radiant heat from other heat
sources.
Do not install the unit in any oily steamy place or near any machine that
generates high frequencies. Doing so may cause a risk of fire, erroneous
operation or dew drop.
Install the unit in a location where the noise from the unit will not be a
problem. (Install indoor unit and BC controller at least 5 m [16-3/8 ft] away
from each other when installed in a space with low background noise, e.g.,
hotel rooms).
Allow enough space and access to ensure water piping, refrigerant piping
and electrical wiring can be easily connected.
Avoid places exposed to the generation, inflow, accumulation or leakage of
flammable and sulfuric gases.
Ensure a downward gradient of at least 1/100 for drain piping.
Properly install the unit on a stable, load-bearing surface.
Some combination of BC controller and outdoor unit cannot be used.
Refer to the table below for details.
Do not install the unit in a place subject to a large amount of steam. Using
the unit in a humid environment may cause condensation during a cooling
operation.
 Combination of BC controller and outdoor unit
Outdoor unit
J type
072 to 126
A
127 to 336
N/A
337 to 432
N/A
4
Model name
TCMBM
TCMBS
1016KA11N4
0104KB11N4
0108KB11N4
Qty
2 kinds
2 kinds
2 kinds
(4 each)
(4 each)
(4 each)
BC controller
JA type
KA type
KB type
A
A
A
A
A
A
N/A
A
A
A:available N/A:Not available

2.2. Commercially available items

The table below lists the items not included in the package but required for in-
stallation, and their required quantity.
Hanging bolt ø10 or Anchor bolt M10
Nut
Double nuts
Insulating material
1. For hanging from the ceiling
[Fig. 3.2.1]
Provide an inspection hole 450 mm [17-23/32 in] square in the ceiling surface
as shown in [Fig.3.2.1].
Install the unit in a suitable location (such as in the ceiling of a corridor or in
the bathroom etc) away from places regularly occupied. Avoid installing in
the center of a room.
Ensure a pull out strength of at least 60 kg [133 LBS] per bolt for hanging
bolts.
Be sure to install BC controllers level.
Install the unit in a location where the noise from the BC controller will not
directly be heard.
Warning:
Be sure to install the unit in a place that can sustain the entire weight.
If there is a lack of strength, it may cause the unit to fall down, resulting in
an injury.
Caution:
Be sure to install the unit level.
4
4
4
1