A.O. Smith 910 ASME Troubleshooting Manual page 14

On-demand water heater
Hide thumbs Also See for 910 ASME:
Table of Contents

Advertisement

3) Verify that the gas supply pressure is within specifications when the heater is in standby and when 
the heater is running.   
4) Check that the clear plastic tube connecting the proportional gas valve to the combustion chamber 
is attached. 
5) The overheat cutoff fuse (OHCF) may have been compromised.  For procedures on how to check 
whether the OHCF is intact, refer to p. 25.  If the OHCF has been compromised, contact the technical 
service department for further assistance. 
6) If flame comes on for only 1‐2 seconds before going out, clean the flame sensor (p. 26). 
7) Check the igniter for a spark.  The spark may be viewed through the sight glass located next to the 
igniter and flame sensor.
a. A strong blue spark will remain steady and in place, while a weak spark will jump around. 
b. If no spark or a weak spark is observed, check the igniter wire connections and make sure these 
are secure.  If these are secure, a replacement igniter will be required. 
8) Check for blockages in the venting, such as bird nests, animals, or trash. 
a. PC Board fault or Gas Solenoid fault.  Contact the technical service department. 
 
ERROR CODE 121:  FLAME LOSS 
This error code appears if the flames disappear while the unit is still supposed to be in operation. 
1) Verify that the hi‐limit switch is not tripped.  Turn the power off to the unit.  Push the white button 
in.  The switch will reset when you hear and feel the button click.  Turn the power back on and test 
the heater.  If the unit fires on, the cause of the hi‐limit trip must be determined.  Please contact the 
technical service department for further technical support.    
2) Check the gas supply.  Verify that sufficient gas is being supplied to the heater and the gas line is 
cleared of debris. 
a. It is possible there is a faulty pressure regulator at the gas meter. 
b. For propane units, colder periods of the day result in a cold regulator and may cause this 
problem. 
3) Verify that the gas supply pressure is within specifications when the heater is in standby and when 
the heater is running. 
4) Check that the clear plastic tube connecting the 
proportional gas valve to the combustion chamber is 
attached.   
5) If the flame comes on for 1‐2 seconds but then goes 
out, clean the flame sensor (p. 27). 
6) The overheat cutoff fuse may have been compromised.  
For procedures on how to check whether the OHCF is 
intact, refer to p. 25. If it has, contact the technical 
service department for further assistance.  
7) Check for blockages in venting, such as bird nests, 
animals, or trash. 
8) PC Board fault or Gas Solenoid fault. 
a. If one of these is suspected to be the problem, 
contact the technical service department. 
 
 
 
14|
Figure 7
Page 
 
Troubleshooting Guide 
Clear pressure hose 
connection 