FGD FlameSpec UV-IR User Manual page 45

Hide thumbs Also See for FlameSpec UV-IR:
Table of Contents

Advertisement

FlameSpec UV-IR User Manual
Medium Sensitivity
Fuel
N-Heptane
Gasoline
Methane
LPG
Diesel
JP5
Kerosene
Methanol
Ethanol
Isopropanol
Polypropylene
Paper
Syngas*
*Syngas mixture: 30% volume methane (CH
Low Sensitivity
Fuel
N-Heptane
LPG
JP5
Methanol
For more information & Technical support: (+1) 714-671-8500 · support@fg-detection.com
Size
1 x 1 ft
1 x 1 ft
32-in Plume
32-in Plume
1 x 1 ft
1 x 1 ft
1 x 1 ft
1 x 1 ft
1 x 1 ft
1 x 1 ft
1 x 1 ft
1 x 1 ft
32-in Plume
), 70% volume hydrogen (H
4
Size
1 x 1 ft
32-in Plume
1 x 1 ft
1 x 1 ft
F110V0020.08
Distance Feet (m)
49 (15)
49 (15)
30 (9)
33 (10)
36 (11)
36 (11)
36 (11)
30 (9)
31 (9.5)
36 (11)
23 (7)
23 (7)
33 (10)
)
2
Distance Feet
Average Response
(m)
Time (Seconds)
16 (5)
0.9
13 (4)
1.0
16 (5)
2.6
10 (3)
1.1
Average Response
Time (Seconds)
1.4
2.7
0.9
1.3
1.6
1.5
1.4
1.3
1.2
1.4
1.7
2.0
1.2
39