Configuration Options; Table 2: Detector Configuration Options - FGD FlameSpec UV-IR User Manual

Hide thumbs Also See for FlameSpec UV-IR:
Table of Contents

Advertisement

FlameSpec UV-IR User Manual

3 Configuration options

Some functions of the detector can be configured using an RS-485 modem connected to a computer
with the "FGD communicator" software. For details of how to download the software please contact
technical support on: (+1) 714-671-8500 or via email at support@fg-detection.com
These configuration options are listed in the following table along with their factory default
values.
Function
Sensitivity
Ultra-fast detection
Alarm Delay
Alarm Latch
Enable Pre-Alarm 0-20mA
Enable dirty window warning 0-
20mA
Aux. Relay
Window Heater
Modbus address
Manual BIT – Alarm Output Test
Note: Medium sensitivity setting allows detection of a 1x1ft
at a distance of 50ft (15m).
For more information & Technical support: (+1) 714-671-8500 · support@fg-detection.com
T
2: D
C
ABLE
ETECTOR
ONFIGURATION
Low, Medium, High, Extreme
Disabled, Enabled
0, 5, 10, 20 or 30 seconds
Disabled, Enabled
Disabled, Enabled
Disabled, Enabled
Alarm
Pre-Alarm
UV Detected
IR Detected
Dirty Window Warning
Disabled, Enabled
1 – 247
Disabled, Enabled
F110V0020.08
O
PTIONS
Options
2
(0.1m
2
) N-heptane pan fire
Default Setting
Medium
Disabled
0 seconds (no delay)
Disabled
Disabled
Disabled
Alarm
Enabled
1
Disabled
23

Advertisement

Table of Contents
loading

This manual is also suitable for:

Flamespec uv-ir-f

Table of Contents