2.10 RS-485 Communication Network

Using the RS-485 network capability of the detector and communicator software, it is possible
to connect up to 32 detectors in an addressable system with only 4 wires (2 for power and 2 for
communication). Using repeaters, the number of detectors can be much larger (32 detectors for
each repeater) up to 247 on the same 4 wires. Using the RS-485 network, it is possible to read
each detector's status (fault, alarm) and to initiate a BIT to each detector individually.
The detector communicates via RS-485 with a Modbus RTU compatible protocol. For more
details on the communication protocol, please see manual F100P0013

Figure 22: RS-485 Networking

2.11 Cabling Recommendations

The cable used should be appropriate for the hazardous area classification and meet local,
national and company regulations.
In order to comply to EMC regulations, the cable must be shielded, and the detector grounded.
The use of industrial grade, suitably armored field cable is recommended). When using HART®
communications, there are some additional considerations. In particular, low capacitance cable
should be used. Further detailed information can be found at the HART® Communication
Foundation's website www.hartcomm.org .
For more information & Technical support: (+1) 714-671-8500 · support@fg-detection.com