Haier GE NAMV1 Series Installation Instructions Manual page 17

One-piece variable speed air handler
Table of Contents

Advertisement

Adjust Jumper
the 1.5 ton unit, for example, that the normal adjustment
setting for heat speed position #4 is 1050 CFM. The +
adjustment setting for that position is 1150 CFM and for
the - adjustment setting is 950 CFM. After the adjustment
setting has been determined, choose the remaining speed
The TEST pin is available to bypass the BDC3 control and
G must be energized for motor to run.
Cool Jumper
The COOL jumper is used to determine the CFM during
electric heat. These jumper selections are activated for
energized.
Blower Performance
NAM24V1 Blower Performance
0 through 0.80 in. w.g. External Static Pressure Range
ADJUST
Jumper Setting
+
NORM
speed setting.
507789-02G / 31-5000673-1
NAMV1 are
"HEAT" Speed
1
2
3
cfm
cfm
cfm
500
705
925
1150
465
650
850
1050
420
600
760
unit.
volume is determined by the control center. The minimum
-030 and -036 units and 450 CFM for -042, -048 and -060
units. This speed is not adjustable. See footnotes in the
call for heating or cooling, the NAMV1
COOL CFM selected.
NOTE:
Jumper Speed Positions
First Stage "COOL" Speed
4
1
2
cfm
cfm
cfm
cfm
365
520
350
485
950
320
425
Issue 2336
Second Stage "COOL" Speed
3
4
1
cfm
cfm
cfm
665
810
500
705
610
740
465
650
560
680
420
600
2
3
4
cfm
cfm
925
1150
850
1050
760
950
Page 17 of 24