Figure 4.6 Chloride tablet dosing system
Install the bromide chloride tablet dosing system DT1:
Attach the bracket in the holes of the frame underneath the evaporative pad.
■
Position the doser so that the bottom of the container is approximately 5 mm/0.2 inch above the bottom
■
of the tray.
If the doser is standing on the bottom of the tray, the water circulation will not be sufficient and the
■
chloride concentration too low.
When the doser is in the correct position, the tablets will be wetted in sequence and the chloride
■
concentration will be correct.
NOTE!
For maintenance, make sure that the holes are not clogged and refill tablets as needed.
TEN-HM3-B1506
Installation