No. 2000-15E General Information Radio Frefrequency Capacitance Type HITROL CO., LTD.
Page 2
HCC-96RF-R General Information The HCC-96RF-R and HLC-96RF-R of material at a point inside the tank, bin level switches are point level devices or other vessel. used to detect the presence or absence Detection circuitry compares the signal impedance of the signal circuit changes flowing from the active sensing probe when material touches the probe.
Page 3
HCC-96RF-R General Information Insert Amplifer (HCC-96RF-R) (Fig. b) Power Supply 15 V DC (From Controller) Output signal 0~5 V DC Max. Oscillation Frequency 153.6 kHz Temperature Range High Sensitivity(1~2 pF) -20 ~+50 Low Sensitivity(3~10 pF) -30 ~+70 We i g h t about 206 g Probe Specification (Fig.
Page 4
HCC-96RF-R General Information The probe should be located out of be mounted so that the material does not I n s t a l l a t i o n direct flow of material while the vessel is build up excessively on the compensation being filled.
Page 5
HCC-96RF-R General Information Top Mounting In case of nozzle, the compensation electrode must be installed min. 100 mm longer than the nozzle length to inside the vessel. (Fig. e) Probe must be installed min. 500 mm from silo. (Fig. f)
Page 6
HCC-96RF-R General Information HCC-96RF-R and HLC-96RF-R are shipped from the factory in the low level fail-safe F a i l - S a f e c o n d i t i o n . S e l e c t i o n...
Page 7
HCC-96RF-R General Information HCC-96RF-R and HLC-96RF are shipped from the Time Delay factory in the minimum time(0.5 sec) delay position. S e t t i n g When used in liquid or agitated material where material movement could cause false or prematrue level indication, an increased time delay volume may be TIME=50x0.2=10 sec...