Operation
Test No.
Input or Test Input
1
V
= 24 V DC
Test
between terminals 3b+, 4a+, and 3a-
2
V
= 24 V DC
Test
between terminals 3b+, 4b+, and 3a-
3
V
= 24 V DC
Test
between terminals 4a+, 4b+, and 3a-
4
V
= 24 V DC
Test
between terminals 4a+, 3b+, 4b+, and 3a-
5
V
= 0 V DC
Test
between terminals 4a+, 3b+, 4b+, and 3a-
6
V
= 24 V DC
input
between terminals 8a+ and 7a- with regular
input polarity
Table 5.3
Expected test results for the proof test of HiC5861
Test No.
Input or Test Input
1
V
= 24 V DC
Test
between terminals 3b+, 4a+, and 3a-
2
V
= 24 V DC
Test
between terminals 3b+, 4b+, and 3a-
3
V
= 24 V DC
Test
between terminals 4a+, 4b+, and 3a-
4
V
= 24 V DC
Test
between terminals 4a+, 3b+, 4b+, and 3a-
5
V
= 0 V DC
Test
between terminals 4a+, 3b+, 4b+, and 3a-
6
V
= 24 V DC
input
between terminals 8a+ and 7a- with regular
input polarity
Table 5.4
Expected test results for the proof test of HiC5861Y1
Only if all tests are successfully done, the proof test is successful.
18
Output (mA)
•
DTS output (terminals 5a, 5b): OL
(overload)
•
LED TST is flashing
•
DTS output (terminals 5a, 5b): OL
(overload)
•
LED TST is flashing
•
DTS output (terminals 5a, 5b): OL
(overload)
•
LED TST is flashing
•
DTS output (terminals 5a, 5b):
shows < 10
•
LED TST is flashing
•
DTS output (terminals 5a, 5b): OL
(overload)
•
LED TST is off
•
DTS output (terminals 5a, 5b):
shows < 10
Output (mA)
•
DTS output (terminals 1a, 5a): OL
(overload)
•
LED TST is flashing
•
DTS output (terminals 1a, 5a): OL
(overload)
•
LED TST is flashing
•
DTS output (terminals 1a, 5a): OL
(overload)
•
LED TST is flashing
•
DTS output (terminals 1a, 5a):
shows < 10
•
LED TST is flashing
•
DTS output (terminals 1a, 5a): OL
(overload)
•
LED TST is off
•
DTS output (terminals 1a, 5a):
shows < 10