Mounting and Installation

4
Mounting and Installation
Mounting and Installing the Device
1.
Observe the safety instructions in the instruction manual.
2.
Observe the information in the manual.
3.
Observe the requirements for the safety loop.
4.
Connect the device only to devices that are suitable for this safety application.
5.
Check the safety function to ensure the expected output behavior.
4.1

Installation

To avoid contact welding we recommend using a serial current limitation in the load circuit.
The KFD0-RSH-1.1D.F1 device is delivered with a replaceable fuse. Replace this fuse only
with a fuse up to 5 AT. Optionally use an unfused terminal with an external current limitation.
The KCD0-RSH-1.1D.1, KCD0-RSH-1.1D.4, HiC5861, and HiC5861Y1 devices are delivered
with an internal fuse. You cannot replace this fuse.
4.2

Configuration

A configuration of the device is not necessary and not possible.