3-2. ELECTRICAL PARTS SPECIFICATIONS
Service Ref.
Symbol
Parts name
Room temperature
TH21
detection thermistor
Pipe temperature
TH22
detection thermistor/liquid
Pipe temperature
TH23
detection thermistor/gas
Fuse
FUSE
(Indoor controller board)
Fan motor
MF
(with thermal fuse)
Vane motor
MV1
(Upper)
Vane motor
MV2
(Lower)
Power supply terminal
TB2
block
Transmission terminal
TB5
block
MA-Remote controller
TB15
terminal block
*Refer to WIRING DIAGRAM for the supplied voltage.
3-3. SOUND PRESSURE LEVEL
PKFY-WL▪NLMU-E
Measurement location
* Measured in anechoic room.
TCH122
PKFY-WL04NLMU-E.TH
PKFY-WL06NLMU-E.TH
PKFY-WL08NLMU-E.TH
Resistance 32°F/15 k", 50°F/9.6 k", 68°F/6.3 k", 77°F/5.4 k", 86°F/4.3 k", 104°F/3.0 k"
Resistance 32°F/15 k", 50°F/9.6 k", 68°F/6.3 k", 77°F/5.4 k", 86°F/4.3 k", 104°F/3.0 k"
Resistance 32°F/15 k", 50°F/9.6 k", 68°F/6.3 k", 77°F/5.4 k", 86°F/4.3 k", 104°F/3.0 k"
1m
PKFY-WL12NLMU-E.TH
PKFY-WL15NLMU-E.TH
T3.15AL250V
8 X 30W / RC0J30-CV
MSBPC20 DC12V
MSBPC20 DC12V
(L1, L2) Rated to 250V 20A *
(M1, M2, S) Rated to 250V 20A *
(1, 2) Rated to 250V 10A *
Sound pressure level at anechoic room : Low-Mid2-Mid1-High
Model name
PKFY-WL04NLMU-E.TH
PKFY-WL06NLMU-E.TH
PKFY-WL08NLMU-E.TH
PKFY-WL12NLMU-E.TH
PKFY-WL15NLMU-E.TH
5
5
Sound pressure level dB (A)
22-26-28-30
22-28-33-36
22-30-36-41
29-34-38-41
30-36-41-45