Shipping and Handling

1. This actuator is shipped in the FULLY CW position (2 color position indicator
shows "CLOSE" and the Reference Dimple aligns with "0"). (The "1" mark is the
FULLY CCW position).
2. NOTE, THIS ACTUATOR MUST HAVE WATER TIGHT EMT FITTINGS, WITH
CONDUIT DRAINAGE INSTALLED AND POWER SUPPLIED TO UNIT TO
KEEP THE HEATER WARM AT THE TIME OF INSTALLATION.
3. Storage: This unit should NOT be stored outside unless it is powered up
and has proper conduit terminations. When NOT powered up, it should be
stored in a clean, dry environment at all times.
4. This actuator has been factory calibrated to operate between 0 degrees and
90 degrees. Most quarter-turn products will not require recalibration of
these settings. If any travel adjustment is necessary, please refer to pages 7-13
for instructions.
5. The actuator CANNOT operate with a rotation greater than 95 degrees.

Product Mounting and Setup

1. Fully CLOSE the valve or damper to which the actuator is to be mounted.
Keep in mind this actuator rotates CW (as viewed from above the unit) when driving CLOSED.
2. Assemble necessary linkage components and attach the actuator to the driven device.
3. Tighten mounting bolts, making sure actuator is centered on the device drive shaft.
4. Utilize the handwheel to check for unobstructed manual operation from fully CCW to fully CW positions
BEFORE applying power to the unit.
5. Make the electrical connections per wiring diagram on page 4.
Connect POWER to terminals marked 1 and 2.
Actuator accepts a 4-20mA (default), 0-10VDC, 1-5VDC, or 2-10VDC signal.
Connect CONTROL wires on the control card (430-10102) to terminals marked ANALOG: IN and COM. The
positive wire MUST connect to IN or the controller will not function.
Wires may be connected on the control card (430-10102) to ANALOG: Out and COM for remote position
sensing.
Terminals 7-12 on the switch card (430-10100) are for the (adjustable) aux switches. They are dry type
Form C rated 10A @ 250vac MAX.
The drain wire on the signal cables must be grounded at ONE END ONLY! (Preferably at the supply end).
6. Do NOT apply power at this time.

Installation Notes

These actuators are designed to be used between a horizontal and upright position. Do NOT mount the assembly
with the actuator top below a horizontal position.
When installing conduit, use proper techniques for entry into the actuator. Use
drip loops to prevent conduit condensate from entering the actuator.
Mechanical travel stops are factory calibrated for 90 degree operation. These
stops are NOT designed to adjust mechanical rotation by more than +/- 3
degrees, they are for positioning the handwheel only.
Both NPT conduit ports MUST use proper equipment to protect the NEMA 4X
integrity of the housing.
The internal heater is to be used in ALL applications.
Do NOT install the actuator outdoors or in humid environments unless it is
powered up and the heater is functioning.
Use proper wire size to prevent actuator failure (see chart on page 4 for proper
wire sizing).
All terminals accept 12-16AWG solid/stranded wire.
Page 3 of 16 P2/3 HV Proportional Series
Identifying Torque Switch Units:
-TS in Product Name on label.
Units with Torque Switches have
additional switches mounted on
the motor plate (see photo).
ISO
Imperial