Also Refer to Additional Instructions Shipped With The
Boiler For Specific Control Operation and Troubleshooting
NOTICE
WARNING
Boiler should be inspected, cleaned
and, if necessary, adjusted once a year.
A qualified service agency should be
called.
TO AVOID PERSONAL INJURY,
BEFORE SERVICING:
1. Disconnect electrical supply.
2. Shut-off gas supply.
3. Allow boiler to cool.
WARNING
Tb avoid personal injury, death or
property damage, keep boiler area
clear and free from combustible ma¬
terials, gasoline and other flammable
vapors and liquids.
Do not block flow of air to boiler. In¬
complete combustion and carbon mon¬
oxide emissions can cause severe
personal injury, death or substantial
property damage.
Do not store sources of hydrocarbons
(i.e., bleaches, cleaners, chemicals,
sprays, paint removers, fabric soften¬
ers, etc.) in boiler area. This can con¬
tribute to shortened boiler/vent
system life.
Suggested Minimum Maintenance Schedule for
Qualified Service Technician Only
Beginning of each heating season:
1. Annual service call by a qualified service agency.
2. Check burners and flueways and clean if necessary. Ref¬
erence "Clean Boiler Heating Surfaces" and "Cleaning
Main Burners," page 15.
3. Visually inspect base insulation. Reference "Inspect Base
Insulation," page 11.
4. Follow procedure "1b Place in Operation," page 11.
5. Visually inspect pilot and burner flames. Reference
"Check Burner Flames," pages 11 and 12.
6. Visually inspect venting system for blockage, deteriora¬
tion or leakage. Reference "Inspect Venting System,"
page 12.
7. Check operation of low-water cut-off, if used, and addi¬
tional field-installed controls. Refer to manufacturer's in¬
structions.
8. Check that boiler area is free from combustible materials,
gasoline and other flammable vapors and liquids.
9. Check for and remove any obstruction to flow of combus¬
tion or ventilation air.
10. Follow instructions on circulator to oil, if oil lubricated.
Overoiling will damage the circulator. Water lubricated
circulators do not need oiling.
Daily during heating season:
1. Check that boiler area is free from combustible materials,
gasoline and other flammable vapors and liquids.
2. Check for and remove any obstruction to the flow of com¬
bustion or ventilation air.
Periodically during heating season:
1. Check relief valve. Reference manufacturer's instructions
on relief valve tag.
2. Tfest low water cut-off, if used. Blowdown if low water cut¬
off is float type. Reference manufacturer's instructions.
Monthly during heating season:
1. Check for leaks in boiler and piping. If found, repair at
WARNING
DANGER
Leaks must be repaired at once.
Failure to do so can damage
boiler, resulting in substantial
property damage.
Do not use petroleum based
cleaning or sealing compounds in
boiler system. Severe damage to
boiler will result, causing sub¬
stantial property damage.
2. Visually inspect pilot and burner flames. Reference
"Check Burner Flames," pages 11 and 12.
3. Visually inspect venting system for blockage, deteriora¬
tion or leakage. Reference "Inspect Venting System,"
page 12.
4. Check automatic air vent for leakage. If leaking, remove
vent cap and push valve core in to wash off sediment that
may have accumulated on valve seat. Release valve,
replace cap and open one turn.
End of each heating season:
1. Follow "Annual Shutdown Procedure," page 15.