Bryant 559K 08 Series Service And Maintenance Instructions
Bryant 559K 08 Series Service And Maintenance Instructions

Bryant 559K 08 Series Service And Maintenance Instructions

Single package rooftop electric cooling unit with puron (r-410a) refrigerant 7.5 to 15 nominal tons
Hide thumbs Also See for 559K 08 Series:
Table of Contents

Advertisement

Quick Links

5 5 9 K * 0 8 - 1 6
S i n g l e P a c k a g e R o o f t o p E l e c t r i c C o o l i n g U n i t
with Pu ro n® ( R- 4 1 0 A) R efr i ger an t
7. 5 t o 15 N o mi na l T o n s
Service and Maintenance Instructions
CONTENTS
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . 1
UNIT ARRANGEMENT AND ACCESS . . . . . . . . . . . . . . 2
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Routine Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
SUPPLY FAN (BLOWER) SECTION . . . . . . . . . . . . . . . . 4
Supply Fan (Direct-Drive) . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2-Speed Indoor Fan Motor . . . . . . . . . . . . . . . . . . . . . . . . 12
COOLING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Condenser Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Recommendation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Evaporator Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Evaporator Coil Metering Devices . . . . . . . . . . . . . . . . . . 14
TXV Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Replacing TXV . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Refrigerant System Pressure Access Ports . . . . . . . . . . . . 14
PURON (R-410A) REFRIGERANT . . . . . . . . . . . . . . . . . 15
Refrigerant Charge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
COMPRESSOR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Lubrication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Replacing Compressor . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Compressor Rotation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Filter Drier . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Condenser-Fan Adjustment . . . . . . . . . . . . . . . . . . . . . . . . 21
Troubleshooting Cooling System . . . . . . . . . . . . . . . . . . . . 22
CONVENIENCE OUTLETS . . . . . . . . . . . . . . . . . . . . . . 23
Convenience Outlets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Installing Weatherproof Cover . . . . . . . . . . . . . . . . . . . . . 23
Non-Powered Type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Unit-Powered Type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Duty Cycle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Fuse on Powered Type . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
ELECTRIC HEATERS . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Completing Heater Installation . . . . . . . . . . . . . . . . . . . . . 25
SMOKE DETECTORS . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Smoke Detector Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Smoke Detector Locations . . . . . . . . . . . . . . . . . . . . . . . . . 26
Detector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
SENSOR AND CONTROLLER TESTS . . . . . . . . . . . . . 30
Sensor Alarm Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Controller Alarm Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Dirty Controller Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Dirty Sensor Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53559012-01
Page
Printed in U.S.A.
Form No. SM559K-8-16-01
Changing the Dirt Sensor Test . . . . . . . . . . . . . . . . . . . . . 30
Remote Station Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
SD-TRK4 Remote Alarm Test Procedure . . . . . . . . . . . . 31
Dirty Sensor Test Using an SD-TRK4 . . . . . . . . . . . . . . . 31
Detector Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
PROTECTIVE DEVICES . . . . . . . . . . . . . . . . . . . . . . . . . 32
Compressor Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Relief Device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Control Circuit, 24-V . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
ECONOMIZER SYSTEMS . . . . . . . . . . . . . . . . . . . . . . . 34
Economi$er X (Factory Option) . . . . . . . . . . . . . . . . . . . . 45
PRE-START-UP/START-UP . . . . . . . . . . . . . . . . . . . . . . 57
START-UP, GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Unit Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Additional Installation/Inspection . . . . . . . . . . . . . . . . . . 57
Return-Air Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Outdoor-Air Inlet Screens . . . . . . . . . . . . . . . . . . . . . . . . . 57
Compressor Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Internal Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Refrigerant Service Ports . . . . . . . . . . . . . . . . . . . . . . . . . 57
Compressor Rotation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Heating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Ventilation (Continuous Fan) . . . . . . . . . . . . . . . . . . . . . . 58
FASTENER TORQUE VALUES . . . . . . . . . . . . . . . . . . . 58
GENERAL FAN PERFORMANCE NOTES . . . . . . . . . 63
NOMENCLATURE . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
APPENDIX B - PHYSICAL DATA . . . . . . . . . . . . . . . . 60
APPENDIX C - FAN PERFORMANCE . . . . . . . . . . . . 63
APPENDIX D - WIRING DIAGRAMS . . . . . . . . . . . . . 84
APPENDIX E - LOW AMBIENT CONTROL SENSOR
LOCATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
START-UP CHECKLIST . . . . . . . . . . . . . . . . . . . . . . . CL-1

SAFETY CONSIDERATIONS

Installation and servicing of air-conditioning equipment can be
hazardous due to system pressure and electrical components. Only
trained and qualified service personnel should install, repair, or
service air-conditioning equipment. Untrained personnel can per-
form the basic maintenance functions of replacing filters. Trained
service personnel should perform all other operations.
When working on air-conditioning equipment, observe precau-
tions in the literature, tags and labels attached to the unit, and
other safety precautions that may apply. Follow all safety codes.
Wear safety glasses and work gloves. Use quenching cloth for
unbrazing operations. Have fire extinguishers available for all
brazing operations.
Follow all safety codes. Wear safety glasses and work gloves. Use
quenching cloth for brazing operations. Have fire extinguisher
Pg 1
11-23
Replaces: New

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the 559K 08 Series and is the answer not in the manual?

Questions and answers

Summary of Contents for Bryant 559K 08 Series

  • Page 1: Table Of Contents

    5 5 9 K * 0 8 - 1 6 S i n g l e P a c k a g e R o o f t o p E l e c t r i c C o o l i n g U n i t with Pu ro n®...
  • Page 2: Unit Arrangement And Access

    available. Read these instructions thoroughly and follow all warn- ings or cautions attached to the unit. Consult local building codes WARNING and National Electrical Code (NEC) for special requirements. Recognize safety information. This is the safety ALERT symbol FIRE, EXPLOSION HAZARD .
  • Page 3: Routine Maintenance

    Routine Maintenance These items should be part of a routine maintenance program, to be checked every month or two, until a specific schedule for each can be identified for this installation: QUARTERLY INSPECTION (AND 30 DAYS AFTER INITIAL START) • Return air filter replacement •...
  • Page 4: Supply Fan (Blower) Section

    To remove the filters: Grasp the bottom flange of the upper panel. Screws Lift up and swing the bottom out until the panel disen- gages and pulls out. Reach inside and extract the filters from the filter rack. Replace these filters as required with similar replacement filters of same size.
  • Page 5 Serial (R/T) WHITE CTL Signal Common BLACK Power L1 PINK 10 vdc Source ORANGE YELLOW Power L2 0-10 vdc signal GRAY Power L3 BLUE 10 11 12 YEL/GRN Earth Ground Safety Relay VIOLET Safety Relay PWM signal Fig. 8 — ECM Motor Plug Connectors EVALUATING MOTOR SPEED The direct drive ECM blower motor uses a constant speed design.
  • Page 6 ESP in. wg Factory Setting: Calculator 9.0 V 1500 Field Setting: 1625 Record field setting here 1750 1875 2000 Switch Range: 2125 10.0 2250 4.1 - 7.5 2375 6.9 - 8.7 2500 7.7 - 10.0 Field Accessories: Economizer * Overlap in A, B, C switch range 1 Stage E Heat designed for maximum field adjustment potential.
  • Page 7 TROUBLESHOOTING THE ECM MOTOR as the voltage/speed programming will not be the same as that on an original factory motor. Axion™ Fan Technology motors are designed with several built- in protections included in the motor software. If the motor detects a fault it will safely shut down.
  • Page 8 Removing the Motor and Fan Assembly NOTE: Due to press fit design of composite Rotor on Motor, it is highly recommended that any time a motor is replaced the fan ro- tor is replaced as well. The rest of the assembly may be reused. See Fig.
  • Page 9 Disassembling Standard/Medium Motor and Fan Assembly Disassembling High Static Motor and Fan Assembly See Fig. 13. See Fig. 14. NOTE: Refer to “Model Number Nomenclature” on page 59, NOTE: Refer to “Model Number Nomenclature” on page 59, position 13 for specific unit requirements. position 13 for specific unit requirements.
  • Page 10 Reassembly of Standard/Medium Motor and Fan Assembly Reassembly of High Static Motor and Fan Assembly See Fig. 15. See Fig. 16. NOTE: Refer to “Model Number Nomenclature” on page 59, NOTE: Refer to “Model Number Nomenclature” on page 59, position 13 for specific unit requirements. position 13 for specific unit requirements.
  • Page 11 Reinstalling Motor and Fan Assembly See Fig. 17. Align motor harness/grommet at ~7 o’clock (facing installer) and align the bottom flats on right and left sides of fan stator with fan deck ribs. Drop fan assembly down into fan deck opening and slide back until aluminum stator is under the rear fan deck brackets.
  • Page 12: 2-Speed Indoor Fan Motor

    2-Speed Indoor Fan Motor PERIODIC CLEAN WATER RINSE All 559K units with Axion™ Fan Technology come factory set to A periodic clean water rinse is very beneficial for coils that are ap- automatically adjust the indoor fan motor speed in sequence with plied in coastal or industrial environments.
  • Page 13 Top Panel Support (Field- Supplied) Center Baffle Fig. 19 — Propping Up Top Panel Remove the compressor access panel to access the lower coil Fig. 21 — Separating Coil Sections clip. The condenser coil corner post may also be removed. (Top View) Remove the screws from both sides of the 4 coil retaining clips on the hairpin end of the coil tube sheets.
  • Page 14: Evaporator Coil

    Thoroughly apply Totaline environmentally balanced coil The pin is spring loaded, which exerts pressure on the under- cleaner solution to all coil surfaces including finned area, side of the diaphragm. Therefore, the bulb pressure works tube sheets and coil headers. against the spring pressure and evaporator suction pressure to Hold garden sprayer nozzle close to finned areas and apply open the valve.
  • Page 15: Puron (R-410A) Refrigerant

    I N S U L A T I O N C O V E R R E M O V E D fer to Bryant GTAC2-5 Charging, Recovery, Recycling and Recla- S U C T I O N L I N E mation training manual and the following procedures.
  • Page 16 COOLING CHARGING CHARTS 7.5 Ton Entry Tier R-410A Charging Chart (Unit must have both compressors and outdoor fans on high speed) 59.9 Add Charge if Above Curve 48.8 37.7 26.6 Remove Charge if Below the Curve 15.5 -6.7 1034 1379 1723 2068 2413...
  • Page 17 COOLING CHARGING CHARTS 8.5 Ton Entry Tier R-410A Charging Chart (Unit must have both compressors and outdoor fans on high speed) 59.9 Add Charge if Above Curve 48.8 37.7 26.6 Remove Charge if Below the Curve 15.5 -6.7 1034 1379 1723 2068 2413...
  • Page 18 COOLING CHARGING CHARTS 10 Ton Entry Tier R-410A Charging Chart (Unit must have both compressors and outdoor fans on high speed) 59.9 Add Charge if Above Curve 48.8 37.7 26.6 Remove Charge if Below the Curve 15.5 -6.7 1034 1379 1723 2068 2413...
  • Page 19 COOLING CHARGING CHARTS 12.5 Ton Entry Tier R-410A Charging Chart (Unit must have both compressors and outdoor fans on high speed) 59.9 Add Charge if Above Curve 48.8 37.7 26.6 Remove Charge if Below the Curve 15.5 -6.7 1034 1379 1723 2068 2413...
  • Page 20 COOLING CHARGING CHARTS 15 Ton 48/50 FC / 582/559 / RGV/RAV (Unit must run in Subcooling mode) 59.9 Add Charge if Above Curve 48.8 37.7 26.6 Remove Charge if Below the Curve 15.5 -6.7 1034 1379 1723 2068 2413 2758 3102 3447 3792...
  • Page 21: Compressor

    COMPRESSOR Compressor Rotation Lubrication CAUTION The compressor is charged with the correct amount of oil at the factory. EQUIPMENT DAMAGE HAZARD Failure to follow this caution can result in premature wear and damage to equipment. CAUTION Scroll compressors can only compress refrigerant if UNIT DAMAGE HAZARD rotating in the right direction.
  • Page 22: Troubleshooting Cooling System

    Troubleshooting Cooling System Refer to Table 2 for additional troubleshooting topics. Table 2 — Troubleshooting SYMPTOM CAUSE SOLUTION Power failure. Call power company. Fuse blown or circuit breaker tripped. Replace fuse or reset circuit breaker. Determine root cause. Defective thermostat, contactor, transformer. Replacement component.
  • Page 23: Convenience Outlets

    CONVENIENCE OUTLETS Loosen the two screws at the GFCI duplex outlet, until approximately 1/2-in. (13 mm) under screw heads is exposed. Press the gasket over the screw heads. Slip the backing plate over the screw heads at the keyhole slots and align WARNING with the gasket;...
  • Page 24: Duty Cycle

    ELECTRIC HEATERS The 559K units can be equipped with field-installed accessory electric heaters. The heaters are modular in design, with heater frames holding open coil resistance wires strung through ceramic insulators and control contactor(s), using a combination of 24-v control side break/auto-reset or line-break/auto-reset limit switches and a pilot-circuit/manual reset limit switch to protect the unit against over-temperature situations.
  • Page 25: Completing Heater Installation

    Stator Manual Reset Limit Switch Heater Module Fig. 35 — Typical Module Installation SINGLE POINT BOXES AND SUPPLEMENTARY FUSES Control Side Line Break Automatic Reset “One Shot” When the unit MOCP device value exceeds 60A, unit-mounted Limit Switches Limit Switches supplementary fuses are required for each heater circuit.
  • Page 26: Smoke Detectors

    SMOKE DETECTORS Smoke detectors are available as factory-installed options on Duct Smoke Sensor 559K models. Smoke detectors may be specified for supply air only, for return air without or with economizer, or in combination of supply air and return air. Return air smoke detectors are ar- ranged for vertical return configurations only.
  • Page 27 Supply Air Smoke Detector Return Air Smoke Detector (As Shipped) Fig. 41 — Typical Supply Air Smoke Detector Sensor Fig. 43 — Typical Return Air Smoke Detector Location Location (size 16 units) RETURN AIR SMOKE DETECTOR SENSOR WITHOUT RETURN AIR SMOKE DETECTOR SENSOR WITH ECONOMIZER ECONOMIZER The sampling tube is located across the return air opening on the...
  • Page 28: Completing Installation Of Return Air Smoke

    Completing Installation of Return Air Smoke Rotate the detector plate so the sensor is facing outwards and the sampling tube connection is on the bottom. See Fig. 46. Detector Use the following steps to complete the installation of the return Return Air Smoke Detector air smoke detector.
  • Page 29: Fiop Smoke Detector Wiring And Response

    FIOP Smoke Detector Wiring and Response HIGHLIGHT B 24-v power signal using the ORN lead is removed at the smoke ALL UNITS detector input on UCB; all unit operations cease immediately. The FIOP smoke detector is configured to automatically shut ADDITIONAL APPLICATION DATA down all unit operations when a smoke condition is detected.
  • Page 30: Sensor And Controller Tests

    SENSOR AND CONTROLLER TESTS Dirty Sensor Test The dirty sensor test provides an indication of the sensor’s ability Sensor Alarm Test to compensate for gradual environmental changes. A sensor that The sensor alarm test checks a sensor’s ability to signal an can no longer compensate for environmental changes is consid- alarm state.
  • Page 31: Remote Station Test

    Remote Station Test The remote station alarm test checks a test/reset station’s ability to IMPORTANT: Failure to follow this ALERT can result in initiate and indicate an alarm state. an unnecessary evacuation of the facility. Holding the test magnet to the target area for longer than seven seconds will put the detector into the alarm state and IMPORTANT: Failure to follow this ALERT can result in an activate all automatic alarm responses.
  • Page 32: Troubleshooting

    ALARM STATE RESETTING ALARM AND TROUBLE CONDITION TRIPS The smoke detector enters the alarm state when the amount of Manual reset is required to restore smoke detector systems to Nor- smoke particulate in the sensor’s sensing chamber exceeds the mal operation. For installations using two sensors, the duct smoke alarm threshold value.
  • Page 33: Relief Device

    MIXED TEMPERATURE SENSOR HIGH PRESSURE SWITCH The Mixed Temperature Sensor (MTS) is installed on the return The system is provided with a high pressure switch mounted on side of the unit filter bracket. See Fig. 51. the discharge line. The switch is stem-mounted and brazed into the discharge tube.
  • Page 34: Economizer Systems

    ECONOMIZER SYSTEMS Outside Air The unit may be equipped with a factory-installed or accessory Temperature Sensor (field-installed) economizer system. Two types are available with EconoMi$er X logic control systems (EconoMi$er X and EconoMi$er IV). See ® Harness Fig. 52 and Fig. 53 for component locations on each type. Economizers use direct-drive damper actuators.
  • Page 35: Economi$Er Iv (Field-Installed Accessory)

    EconoMi$er IV (Field-Installed Accessory) IMPORTANT: For 559K*08-16 rooftop units EconoMi$er IV is available as a field-installed accessory only. ECONOMI$ER IV STANDARD SENSORS Troubleshooting instructions are enclosed. A functional view of the EconoMi$er ® IV accessory is shown in Fig. 54. Typical set- tings, sensor ranges, and jumper positions are also shown.
  • Page 36 Table 6 — EconoMi$er IV Input/Output Logic INPUTS OUTPUTS Demand Enthalpy Compressor N Terminal Controlled Ventilation Outdoor Return Stage 1 Stage 2 Occupied Unoccupied (DCV) High (Free Cooling Minimum position Closed LED Off) Below Set (DCV LED Off) Modulating (between Modulating (between min.
  • Page 37 The temperature sensor looks like an eyelet terminal with wires running to it. The sensor is located in the “crimp end” and is sealed DIP Switch Changeover from moisture. Position Temperature Outdoor Air Lockout Sensor 48°F The EconoMi$er IV is equipped with an ambient temperature 1 2 3 lockout switch located in the outdoor airstream which is used to lock out the compressors below a 42°F (6°C) ambient tempera-...
  • Page 38 7.5 and 8.5 Ton Units 10 and 12.5 Ton Units Pressure Drop for Electric Heat, 10 to 12.5 Ton Units Pressure Drop for Electric Heat, 7.5 to 8.5 Ton Units 0.25 0.12 0.10 0.20 0.08 0.15 0.06 0.10 0.04 0.05 0.02 0.00 0.00...
  • Page 39 Horizontal Economizer Barometric Relief Vertical Economizer Barometric Relief Vertical Economizer Barometric Relief Flow Horizontal Economizer Barometric Relief Flow 2500 2500 2000 2000 1500 1500 1000 1000 0.00 0.05 0.10 0.15 0.20 0.25 0.30 0.00 0.05 0.10 0.15 0.20 0.25 0.30 Return Duct Static Pressure (in.
  • Page 40 Horizontal Economizer Barometric Relief Vertical Economizer Barometric Relief Vertical Economizer Barometric Relief Flow Horizontal Economizer Barometric Relief Flow 2500 2500 2000 2000 1500 1500 1000 1000 0.00 0.05 0.10 0.15 0.20 0.25 0.30 0.00 0.05 0.10 0.15 0.20 0.25 0.30 Return Duct Static Pressure (in.
  • Page 41 EconoMi$er IV Controller Dehumidification Coil Pressure Drop, 7.5 Ton Unit EconoMi$er IV 0.30 0.25 0.20 0.15 Grommet 0.10 0.05 0.00 1000 2000 3000 4000 5000 Return Air Unit Airflow (cfm) Sensor Return Duct (Field-Provided) Dehumidification Coil Pressure Drop, 8.5, 10 and 12.5 Ton Units Fig.
  • Page 42 Exhaust Set Point Adjustment The exhaust set point will determine when the exhaust fan runs (29) (32) (35) (38) (41) (43) based on damper position (if accessory power exhaust is in- CONTROL POINT stalled). The set point is modified with the Exhaust Fan set point CONTROL APPROX.
  • Page 43 TR and N. When the timeclock Use setting 1 or 2 for Bryant equipment: contacts are closed, the EconoMi$er IV control will be in occu- pied mode. When the timeclock contacts are open (removing Press Clear and Mode buttons.
  • Page 44 10. Set DCV maximum position potentiometer fully CW DCV MINIMUM AND MAXIMUM POSITION (clockwise). To check the DCV minimum and maximum position: 11. Set enthalpy potentiometer to D. Make sure EconoMi$er IV preparation procedure has been 12. Apply power (24 vac) to terminals TR and TR1. performed.
  • Page 45: Economi$Er X (Factory Option)

    Economi$er X (Factory Option) SPECIFICATIONS The EconoMi$er X system is an expandable economizer control W7220 Economizer Module ® system, which includes a W7220 economizer module (controller) The module is designed for use with 2 to 10 vdc or bus communi- with an LCD and keypad (see Fig.
  • Page 46 OUTPUTS Storage Temperature –40 to 150°F (–40 to 65°C) Actuator Signal Shipping Temperature 2-10 vdc; minimum actuator impedance is 2k ohm; bus two-wire output for bus communicating actuators. –40 to 150°F (–40 to 65°C) Exhaust fan, Y1, Y2 and AUX1 O Relative Humidity All Relay Outputs (at 30 vac): 5% to 95% RH non-condensing...
  • Page 47 Table 9 — Economizer Module-Right Hand Terminal Blocks LABEL TYPE DESCRIPTION Top Right Terminal Blocks AUX2 I 24 vac IN The first terminal is not used. Shut Down (SD) or HEAT (W) Conventional only AUX2- 24 vac IN Heat Pump Changeover (O-B) in Heat Pump mode.
  • Page 48 User Interface Table 10 — HH57AC081 Sensor Wiring Terminations The user interface consists of a 2-line LCD display and a 4-button keypad on the front of the economizer controller. TERMINAL TYPE DESCRIPTION Keypad NUMBER LABEL Use the four navigation buttons (see Fig. 73) to scroll through the S-BUS Communications menus and menu items, select menu items, and to change parame-...
  • Page 49 Menu Structure Setup and Configuration Table 12 illustrates the complete hierarchy of menus and parame- Before being placed into service, the W7220 Economizer module ters for the EconoMi$er X system. must be set up and configured for the installed system. ®...
  • Page 50 Table 12 — W7220 Menu Structure a,b,c,d,e PARAMETER PARAMETER EXPANDED PARAMETER NAME MENU PARAMETER DEFAULT RANGE AND NOTES VALUE INCREMENT SPACE/RETURN AIR CO IN CO2 _ _ _ ppm 0 to 2000 ppm Displays value of measured CO from CO sensor.
  • Page 51 Table 12 — W7220 Menu Structure a,b,c,d,e PARAMETER PARAMETER EXPANDED PARAMETER NAME MENU PARAMETER DEFAULT RANGE AND NOTES VALUE INCREMENT DCV MINIMUM DAMPER POSITION AT LOW SPEED. Only displays if unit is set for 2 speed or 3 speed with 1 heat and 2 cool. IF using 2 speed with 1 VENTMIN L 3.7 V 2 to 10 vdc...
  • Page 52 Table 12 — W7220 Menu Structure a,b,c,d,e PARAMETER PARAMETER EXPANDED PARAMETER NAME MENU PARAMETER DEFAULT RANGE AND NOTES VALUE INCREMENT 35 to 55°F; SUPPLY AIR TEMPERATURE LOW LIMIT MA LO SET 45°F Incremented by Temperature to achieve Freeze Protection (close damper and alarm if temperature falls below setup value).
  • Page 53 Table 12 — W7220 Menu Structure a,b,c,d,e PARAMETER PARAMETER EXPANDED PARAMETER NAME MENU PARAMETER DEFAULT RANGE AND NOTES VALUE INCREMENT SENSOR ERROR CO2 SENS ERR sensor has failed, gone out of range or become disconnected - check wiring then replace sensor if the alarm continues. OA SYLK T ERR OUTSIDE AIR S-BUS SENSOR ERROR Outdoor air enthalpy sensor has failed or become disconnected - check...
  • Page 54 Enthalpy Settings Table 13 — Fan Speed When the OA temperature, enthalpy and dew point are below the respective setpoints, the Outdoor Air can be used for econo- STATE FAN SPEED mizing. Figure 74 shows the new single enthalpy boundaries in the W7220.
  • Page 55 Table 15 — Economizer Operation - FAN TYPE = 2SPEED INPUTS OUTPUTS DEMAND DAMPER POSITION OUTSIDE AIR FAN SPEED CONTROLLED COOL COOL COOL COOL GOOD TO (reference VENTILATION (HEAT ON) Y1-IN Y2-IN Y1-OUT Y2-OUT OCCUPIED UNOCCUPIED ECONOMIZE only) (DCV) HIGH MIN POS H Closed MIN POS L...
  • Page 56 CHECKOUT To perform a Checkout test: Scroll to the desired test in the Checkout menu using the ▲ Inspect all wiring connections at the economizer module’s termi- and ▼ buttons. nals, and verify compliance with the installation wiring diagrams. Press the (Enter) button to select the item.
  • Page 57: Pre-Start-Up/Start-Up

    PRE-START-UP/START-UP Make the following inspections: a. Inspect for shipping and handling damages such as bro- ken lines, loose parts, or disconnected wires, etc. WARNING b. Inspect for oil at all refrigerant tubing connections and on unit base. Detecting oil generally indicates a refriger- PERSONAL INJURY HAZARD ant leak.
  • Page 58: Compressor Rotation

    Compressor Rotation To shut off unit, set system selector switch at OFF position. Reset- ting thermostat at a position above room temperature shuts unit off temporarily until space temperature exceeds thermostat setting. CAUTION Heating EQUIPMENT DAMAGE HAZARD To start unit, turn on main power supply. Set system selector switch to the HEAT position and set thermostat at a setting above Failure to follow this caution can result in premature wear room temperature.
  • Page 59: Appendix A - Model Number

    APPENDIX A — MODEL NUMBER NOMENCLATURE Position: 9 10 11 12 13 14 15 16 17 Example: Unit Type Packaging and Control 559 = Cooling RTU with Optional A = Standard Packaging, electromechanical Electric Heat, Legacy™ Line controls, no intake or exhaust option. Will allow for use of all field-installed econo- mizers, manual or two-position damper.
  • Page 60: Appendix B - Physical Data

    APPENDIX B — PHYSICAL DATA 559K 7.5 to 8.5 Ton Physical Data UNIT 559K*08N 559K*08R 559K*09N 559K*09R NOMINAL TONS BASE UNIT OPERATING WT (lb) REFRIGERATION SYSTEM No. Circuits / No. Compressors / Type 1 / 2 / Scroll 1 / 2 / Scroll 1 / 2 / Scroll 1 / 2 / Scroll Puron...
  • Page 61 APPENDIX B — PHYSICAL DATA (cont) 559K 10 to 12.5 Ton Physical Data UNIT 559K*12N 559K*12R 559K*14N 559K*14R 12.5 12.5 NOMINAL TONS 1041 1041 BASE UNIT OPERATING WT (lb) REFRIGERATION SYSTEM No. Circuits / No. Compressors / Type 1 / 2 / Scroll 1 / 2 / Scroll 1 / 2 / Scroll 1 / 2 / Scroll...
  • Page 62 APPENDIX B — PHYSICAL DATA (cont) 559K 15 Ton Physical Data UNIT 559K*16N 559K*16R NOMINAL TONS 1325 1325 BASE UNIT OPERATING WT (lb) REFRIGERATION SYSTEM No. Circuits / No. Compressors / Type 1 / 2 / Scroll 1 / 2 / Scroll Puron (R-410A) Charge (lb-oz) 24-0...
  • Page 63: General Fan Performance Notes

    APPENDIX C — FAN PERFORMANCE GENERAL FAN PERFORMANCE NOTES The Fan Performance tables offer motor/drive recommenda- tions. In cases when two motor/drive combinations would Interpolation is permissible. Do not extrapolate. work, the lower horsepower option is recommended. External static pressure is the static pressure difference The EPACT (Energy Policy Act of 1992) regulates energy between the return duct and the supply duct plus the static requirements for specific types of indoor fan motors.
  • Page 64 APPENDIX C — FAN PERFORMANCE (cont) 559K*08 — 7.5 Ton Vertical Supply (rpm - bhp) AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 0.34 1102 0.50 1216 0.68 1319 0.86 1414 1.07 2250 1031 0.41 1157 0.58 1267 0.76 1367 0.96 1459 1.17 2440 1092...
  • Page 65 APPENDIX C — FAN PERFORMANCE (cont) 559K*08 – High Static — 7.5 Ton Vertical Supply (rpm - vdc) AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 2250 1102 1216 1319 1414 2440 1031 1157 1267 1367 1459 2625 1092 1213 1320 1416 1506 2810 1155...
  • Page 66 APPENDIX C — FAN PERFORMANCE (cont) 559K*09 — 8.5 Ton Vertical Supply (rpm - bhp) AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 1015 0.39 1128 0.53 1233 0.69 1330 0.87 1421 1.06 2550 1084 0.47 1190 0.62 1289 0.78 1382 0.96 1470 1.16 2760...
  • Page 67 APPENDIX C — FAN PERFORMANCE (cont) 559K*09 – High Static — 8.5 Ton Vertical Supply (rpm - vdc) AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 1015 1128 1233 1330 1421 2550 1084 1190 1289 1382 1470 2760 1154 1253 1348 1437 1521 2975 1225...
  • Page 68 APPENDIX C — FAN PERFORMANCE (cont) 559K*12 — 10 Ton Vertical Supply (rpm - bhp) AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 1181 0.60 1279 0.77 1372 0.95 1461 1.14 1544 1.35 3000 1264 0.73 1356 0.91 1443 1.09 1527 1.29 1607 1.51 3250...
  • Page 69 APPENDIX C — FAN PERFORMANCE (cont) 559K*12 – High Static — 10 Ton Vertical Supply (rpm - vdc) AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 1181 1279 1372 1461 1544 3000 1264 1356 1443 1527 1607 3250 1348 1434 1517 1596 1673 3500 1433...
  • Page 70 APPENDIX C — FAN PERFORMANCE (cont) 559K*14 — 12.5 Ton Vertical Supply (rpm - bhp) AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 1178 0.86 1287 1.12 1386 1.40 1475 1.69 1558 1.99 3750 1260 1.05 1362 1.32 1456 1.62 1543 1.92 1623 2.24 4060...
  • Page 71 APPENDIX C — FAN PERFORMANCE (cont) 559K*14 – High Static — 12.5 Ton Vertical Supply (rpm - vdc) AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 1178 1287 1386 1475 1558 3750 1260 1362 1456 1543 1623 4060 1343 1438 1528 1612 1690 4375 1426...
  • Page 72 APPENDIX C — FAN PERFORMANCE (cont) 559K*16 — 15 Ton Vertical Supply (rpm - bhp) AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 1120 0.73 1201 0.90 1281 1.10 1361 1.32 1441 1.56 4500 1208 0.92 1283 1.10 1357 1.30 1431 1.52 1505 1.77 4875...
  • Page 73 APPENDIX C — FAN PERFORMANCE (cont) 559K*16 – High Static — 15 Ton Vertical Supply (rpm - vdc) AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 1120 1201 1281 1361 1441 4500 1208 1283 1357 1431 1505 4875 1297 1367 1436 1504 1573 5250 1387...
  • Page 74 APPENDIX C — FAN PERFORMANCE (cont) 559K*08 — 7.5 Ton Horizontal Supply (rpm - bhp) AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 0.28 1046 0.43 1167 0.60 1276 0.78 1376 0.98 2250 0.34 1095 0.49 1211 0.67 1316 0.86 1414 1.06 2440 1023 0.40...
  • Page 75 APPENDIX C — FAN PERFORMANCE (cont) 559K*08 – High Static — 7.5 Ton Horizontal Supply (rpm - vdc) AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 1046 1167 1276 1376 2250 1095 1211 1316 1414 2440 1023 1145 1256 1359 1453 2625 1081 1197 1304...
  • Page 76 APPENDIX C — FAN PERFORMANCE (cont) 559K*09 — 8.5 Ton Horizontal Supply (rpm - bhp) AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 0.31 1065 0.45 1178 0.60 1284 0.78 1382 0.97 2550 1010 0.38 1120 0.51 1226 0.67 1327 0.85 1422 1.05 2760 1074...
  • Page 77 APPENDIX C — FAN PERFORMANCE (cont) 559K*09 – High Static — 8.5 Ton Horizontal Supply (rpm - vdc) AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 1065 1178 1284 1382 2550 1010 1120 1226 1327 1422 2760 1074 1177 1277 1373 1464 2975 1139 1235...
  • Page 78 APPENDIX C — FAN PERFORMANCE (cont) 559K*12 — 10 Ton Horizontal Supply (rpm - bhp) AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 1100 0.49 1202 0.64 1301 0.81 1396 1.00 1487 1.21 3000 1176 0.59 1270 0.74 1363 0.92 1453 1.11 1539 1.32 3250...
  • Page 79 APPENDIX C — FAN PERFORMANCE (cont) 559K*12 – High Static — 10 Ton Horizontal Supply (rpm - vdc) AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 1100 1202 1301 1396 1487 3000 1176 1270 1363 1453 1539 3250 1252 1341 1428 1512 1595 3500 1330...
  • Page 80 APPENDIX C — FAN PERFORMANCE (cont) 559K*14 — 12.5 Ton Horizontal Supply (rpm - bhp) AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 1072 0.65 1166 0.83 1266 1.07 1363 1.33 1454 1.62 3750 1148 0.79 1233 0.98 1324 1.22 1416 1.49 1504 1.78 4060...
  • Page 81 APPENDIX C — FAN PERFORMANCE (cont) 559K*14 – High Static — 12.5 Ton Horizontal Supply (rpm - vdc) AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 1072 1166 1266 1363 1454 3750 1148 1233 1324 1416 1504 4060 1226 1303 1386 1472 1556 4375 1304...
  • Page 82 APPENDIX C — FAN PERFORMANCE (cont) 559K*16 — 15 Ton Horizontal Supply (rpm - bhp) AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 1117 0.73 1198 0.90 1278 1.09 1358 1.31 1438 1.55 4500 1205 0.91 1279 1.09 1353 1.29 1427 1.51 1501 1.76 4875...
  • Page 83 APPENDIX C — FAN PERFORMANCE (cont) 559K*16 – High Static — 15 Ton Horizontal Supply (rpm - vdc) AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 1117 1198 1278 1358 1438 4500 1205 1279 1353 1427 1501 4875 1294 1363 1432 1500 1569 5250 1383...
  • Page 84: Appendix D - Wiring Diagrams

    APPENDIX D — WIRING DIAGRAMS 559K*08-16 — Wiring Diagrams — Standard/Medium SCCR SIZE VOLTAGE CONTROL PAGE POWER PAGE 208/230-3-60 559K*08-12 48TM005717 Electro-Mechanical 460-3-60 48TM005715 W7220 Controller 575-3-60 48TM005994 208/230-3-60 48TM005988 559K*14 Electro-Mechanical 460-3-60 48TM005985 48TM005987 W7220 Controller 575-3-60 208/230-3-60 559K*16 50TM001913 Electro-Mechanical 460-3-60...
  • Page 85 APPENDIX D — WIRING DIAGRAMS (cont) Fig. B — 559K*08-12 Control Wiring Diagram — 208/230, 460, 575-3-60 Unit Electro-Mechanical with W7220 Control — Standard/Medium and High SCCR...
  • Page 86 APPENDIX D — WIRING DIAGRAMS (cont) Fig. C — 559K*14 Control Wiring Diagram — 208/230, 460, 575-3-60 Unit Electro-Mechanical with W7220 Control — Standard/Medium and High SCCR...
  • Page 87 APPENDIX D — WIRING DIAGRAMS (cont) Fig. D — 559K*16 Control Wiring Diagram — 208/230, 460, 575-3-60 Unit Electro-Mechanical with W7220 Control — Standard/Medium and High SCCR...
  • Page 88 APPENDIX D — WIRING DIAGRAMS (cont) Fig. E — 559K*08-12 Power Wiring Diagram — 208/230, 460-3-60 Unit Electro-Mechanical with W7220 Control — Standard/Medium SCCR...
  • Page 89 APPENDIX D — WIRING DIAGRAMS (cont) Fig. F — 559K*08-12 Power Wiring Diagram — 575-3-60 Unit Electro-Mechanical with W7220 Control — Standard/Medium SCCR...
  • Page 90 APPENDIX D — WIRING DIAGRAMS (cont) Fig. G — 559K*14 Power Wiring Diagram — 208/230-3-60 Unit Electro-Mechanical with W7220 Control — Standard/Medium SCCR...
  • Page 91 APPENDIX D — WIRING DIAGRAMS (cont) Fig. H — 559K*14 Power Wiring Diagram — 460, 575-3-60 Unit Electro-Mechanical with W7220 Control — Standard/Medium SCCR...
  • Page 92 APPENDIX D — WIRING DIAGRAMS (cont) Fig. I — 559K*16 Power Wiring Diagram — 208/230, 460-3-60 Unit Electro-Mechanical with W7220 Control — Standard/Medium SCCR...
  • Page 93 APPENDIX D — WIRING DIAGRAMS (cont) Fig. J — 559K*16 Power Wiring Diagram — 575-3-60 Unit Electro-Mechanical with W7220 Control — Standard/Medium SCCR...
  • Page 94 APPENDIX D — WIRING DIAGRAMS (cont) Fig. K — 559K*08-12 Control Wiring Diagram — 208/230, 460-3-60 Unit Electro-Mechanical with W7220 Control — High SCCR...
  • Page 95 APPENDIX D — WIRING DIAGRAMS (cont) Fig. L — 559K*14 Control Wiring Diagram — 208/230-3-60 Unit Electro-Mechanical with W7220 Control — High SCCR...
  • Page 96 APPENDIX D — WIRING DIAGRAMS (cont) Fig. M — 559K*14 Control Wiring Diagram — 460-3-60 Unit Electro-Mechanical with W7220 Control — High SCCR...
  • Page 97 APPENDIX D — WIRING DIAGRAMS (cont) Fig. N — 559K*16 Control Wiring Diagram — 208/230, 460-3-60 Unit Electro-Mechanical with W7220 Control — High SCCR...
  • Page 98: Location

    APPENDIX E — LOW AMBIENT CONTROL SENSOR LOCATION T O P O F C O I L T O P O F C O I L S E N S O R P O S I T I O N 4 T H I N T E R M E D I A T E S E N S O R P O S I T I O N F R O M T O P...
  • Page 99: Start-Up Checklist

    START-UP CHECKLIST 559K*08-16 Single Package Rooftop Electric Cooling Units (Remove and use for job file) NOTE: To avoid injury to personnel and damage to equipment or property when completing the procedures listed in this start-up checklist, use good judgment, follow safe practices, and adhere to the safety considerations/information as outlined in preceding sec- tions of this Installation Instruction document.
  • Page 100 PRESSURES Refrigerant Suction STAGE 1 _____________ PSIG STAGE 2 _____________ PSIG Refrigerant Discharge STAGE 1 _____________ PSIG STAGE 2 _____________ PSIG Verify Refrigerant Charge using Charging Charts (Y/N) _____ GENERAL Economizer minimum vent and changeover settings to job requirements (if equipped) (Y/N) _____ Verify smoke detector unit shutdown by utilizing magnet test (Y/N) _____...

This manual is also suitable for:

559k 16 series

Table of Contents