Puron (R-410A) Refrigerant; Refrigerant Charge - Bryant 559K 08 Series Service And Maintenance Instructions

Single package rooftop electric cooling unit with puron (r-410a) refrigerant 7.5 to 15 nominal tons
Table of Contents

Advertisement

Fig. 22 — TXV Valve and Sensing Bulb Location

PURON (R-410A) REFRIGERANT

This unit is designed for use with Puron
Do not use any other refrigerant in this system.
Puron (R-410A) refrigerant is provided in pink (rose) colored cyl-
inders. These cylinders are available with and without dip tubes;
cylinders with dip tubes will have a label indicating this feature.
For a cylinder with a dip tube, place the cylinder in the upright po-
sition (access valve at the top) when removing liquid refrigerant
for charging. For a cylinder without a dip tube, invert the cylinder
(access valve on the bottom) when removing liquid refrigerant.
Because Puron (R-410A) refrigerant is a blend, it is strongly rec-
ommended that refrigerant always be removed from the cylinder
as a liquid. Admit liquid refrigerant into the system in the dis-
charge line. If adding refrigerant into the suction line, use a com-
mercial metering/expansion device at the gauge manifold; remove
liquid from the cylinder, pass it through the metering device at the
gauge set and then pass it into the suction line as a vapor. Do not
remove Puron (R-410A) refrigerant from the cylinder as a vapor.
SEAT
5/8" HEX
0.47
1. Third-party trademarks and logos are the property of their respective owners.
V I E W W I T H T X V B U L B
I N S U L A T I O N C O V E R R E M O V E D
S U C T I O N L I N E
B U L B C A P I L L A R Y T U B E
T X V B U L B
T X V B U L B P R O C E S S T U B E
®
(R-410A) refrigerant.
1/2-20 UNF RH
0.596
30°
This surface provides a metal to metal seal when
torqued into the seat. Appropriate handling is
required to not scratch or dent the surface.
Fig. 23 — CoreMax™

Refrigerant Charge

Amount of refrigerant charge is listed on the unit's nameplate. Re-
fer to Bryant GTAC2-5 Charging, Recovery, Recycling and Recla-
mation training manual and the following procedures.
Unit panels must be in place when unit is operating during the
charging procedure.
NO CHARGE
Use standard evacuating techniques. After evacuating system,
weigh in the specified amount of refrigerant.
LOW-CHARGE COOLING
Using Cooling Charging Charts, Fig. 24-28, vary refrigerant until
the conditions of the appropriate chart are met. Note the charging
charts are different from type normally used. Charts are based on
charging the units to the correct sub-cooling for the various operat-
ing conditions. Accurate pressure gauge and temperature sensing
device are required. Connect the pressure gauge to the service port
on the liquid line. Mount the temperature sensing device on the
liquid line and insulate it so that outdoor ambient temperature does
not affect the reading. Indoor-air cfm must be within the normal
operating range of the unit.
UNIT SIZE DESIGNATION
559K*08
559K*09
559K*12
559K*14
559K*16
EXAMPLE:
Model
Outdoor Temperature
Suction Pressure
Suction Temperature should be
USING COOLING CHARGING CHARTS
Take the outdoor ambient temperature and read the liquid pressure
gauge. Refer to chart to determine what liquid temperature should
be. If liquid temperature is low, add refrigerant. If liquid tempera-
ture is high, carefully recover some of the charge. Recheck the liq-
uid pressure as charge is adjusted.
CORE
(Part No. EC39EZ067)
Washer
O-Ring
1/2" HEX
1
Access Port Assembly
15
NOMINAL TONS REFERENCE
7.5
8.5
10.0
12.5
15.0
559K*08
85°F (29°C)
140 psig (965 kPa)
65°F (16°C)
45°
Depressor per AHRI 720
+.01/–.035
From Face of Body
7/16-20 UNF RH

Advertisement

Table of Contents
loading

This manual is also suitable for:

559k 16 series

Table of Contents