Bryant Legacy 559K 08 Series Installation Instructions Manual
Bryant Legacy 559K 08 Series Installation Instructions Manual

Bryant Legacy 559K 08 Series Installation Instructions Manual

Single package rooftop cooling only with puron (r-410a) refrigerant
Hide thumbs Also See for Legacy 559K 08 Series:
Table of Contents

Advertisement

Quick Links

Legacy™ Line
559K 08-14
Single Package Rooftop Cooling Only
with Puron
(R-410A) Refrigerant
®
CONTENTS
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . 1
Rated Indoor Airflow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Jobsite Survey . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Step 1 - Plan for Unit Location . . . . . . . . . . . . . . . . . . . . 10
Step 3 - Inspect Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Step 4 - Provide Unit Support . . . . . . . . . . . . . . . . . . . . . 10
Step 5 - Field Fabricate Ductwork . . . . . . . . . . . . . . . . . 12
Step 6 - Rig and Place Unit . . . . . . . . . . . . . . . . . . . . . . . 12
(when required) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Step 8 - Install Outside Air Hood . . . . . . . . . . . . . . . . . . 14
Step 10 - Make Electrical Connections . . . . . . . . . . . . . 15
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53559009-01
Installation Instructions
Page
Printed in U.S.A.
Form II559K-8-14-01 Rev. B
EconoMi$er® X (Factory Option) . . . . . . . . . . . . . . . . . . 27
• INPUTS
Smoke Detectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Step 12 - Install Accessories . . . . . . . . . . . . . . . . . . . . . . 40
Step 13 - Fan Speed Set Up . . . . . . . . . . . . . . . . . . . . . . . 40
START-UP CHECKLIST . . . . . . . . . . . . . . . . . . . . . . CL-1

SAFETY CONSIDERATIONS

Installation and servicing of air-conditioning equipment can be
hazardous due to system pressure and electrical components.
Only trained and qualified service personnel should install,
repair, or service air-conditioning equipment.
Untrained personnel can perform basic maintenance functions
of cleaning coils and filters and replacing filters. All other
operations should be performed by trained service personnel.
When working on air-conditioning equipment, observe
precautions in the literature, tags and labels attached to the
unit, and other safety precautions that may apply.
Follow all safety codes, including ANSI (American National
Standards Institute) Z223.1. Wear safety glasses and work
gloves. Use quenching cloth for unbrazing operations. Have
fire extinguisher available for all brazing operations.
It is important to recognize safety information. This is the
safety-alert symbol
. When you see this symbol on the unit
and in instructions or manuals, be alert to the potential for
personal injury.
Understand the signal
CAUTION, and NOTE. These words are used with the safety-
alert symbol. DANGER identifies the most serious hazards
which will result in severe personal injury or death.
WARNING signifies hazards which could result in personal
injury or death. CAUTION is used to identify unsafe practices,
Pg 1
words
DANGER, WARNING,
4-22
Replaces: New

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Legacy 559K 08 Series and is the answer not in the manual?

Questions and answers

Summary of Contents for Bryant Legacy 559K 08 Series

  • Page 1: Table Of Contents

    Legacy™ Line 559K 08-14 Single Package Rooftop Cooling Only with Puron (R-410A) Refrigerant ® Installation Instructions CONTENTS EconoMi$er® X (Factory Option) ....27 •...
  • Page 2: Model Number Nomenclature And Dimensions

    which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions CAUTION which will result in enhanced installation, reliability, or operation. PERSONAL INJURY HAZARD Failure to follow this caution may result in personal injury. DANGER Sheet metal parts may have sharp edges or burrs.
  • Page 3 Position: 9 10 11 12 13 14 15 16 17 Example: Unit Type Packaging and Control Cooling RTU with optional A = Standard Packaging, electro-mechanical Electric Heat, Legacy™ Line controls, no intake or exhaust option. Will allow for use of all field-installed economizers, manual or 2-position damper.
  • Page 4 Fig. 2 — 559K 08-12 Unit Dimensional Drawing...
  • Page 5 Fig. 2 — 559K 08-12 Unit Dimensional Drawing (cont)
  • Page 6 Fig. 2 — 559K 08-12 Unit Dimensional Drawing (cont)
  • Page 7 Fig. 3 — 559K 14 Unit Dimensional Drawing...
  • Page 8 Fig. 3 — 559K 14 Unit Dimensional Drawing (cont)
  • Page 9 Fig. 3 — 559K 14 Unit Dimensional Drawing (cont)
  • Page 10: Installation

    INSTALLATION Make electrical connections Install other accessories Jobsite Survey PAD-MOUNTED INSTALLATION Complete the following checks before installation. Prepare pad and unit supports Consult local building codes and the NEC (National Elec- Check and tighten the bottom condensate drain connection trical Code) ANSI/NFPA 70 for special installation plug requirements.
  • Page 11 ROOF CURB POWER WIRING CONTROL WIRING ACCESSORY CONVENIENCE NOTES: CONNECTOR PKG. ACC. GAS CONNECTION TYPE GAS FITTING ACCESSORY # 1. ROOFCURB ACCESSORY IS SHIPPED DISASSEMBLED. FITTING FITTING OUTLET WIRING CONNECTOR 2. INSULATED PANELS: 25.4 [1"] THK. POLYURETHANE FOAM, 44.5 [1-3/4] # DENSITY. 14"...
  • Page 12: Slab Mount (Horizontal Units Only)

    FOR UNITS WITH ACCESSORY ELECTRIC HEATERS All installations require a minimum clearance to combustible surfaces of 1-in. (25 mm) from duct for first 12-in. (305 mm) away from unit. Outlet grilles must not lie directly below unit discharge. WARNING PERSONAL INJURY HAZARD Failure to follow this warning could cause personal injury.
  • Page 13: Step 7 - Convert To Horizontal And Connect Ductwork

    "B" Place All Seal Strip In Place Detail "A" 36"-54" Required Before Placing Unit On Roof Curb (914-1371) Spreader Bars Duct End "C" Side "A" See Detail "A" DIMENSIONS UNIT MAX WEIGHT 559K*08 1232 88.0 2235 40.0 1015 41.5 1055 559K*09 1353 88.0...
  • Page 14: Step 8 - Install Outside Air Hood

    Locate the (2) screws holding the metal tray to the basepan Screws and remove. Locate and cut the (2) plastic tie-wraps secur- ing the assembly to the damper. (See Fig. 11.) Be careful to not damage any wiring or cut tie-wraps securing any wiring. Hood Parts Duct Covers Sheet Metal...
  • Page 15: Step 9 - Install External Condensate Trap And Line

    Panel Indoor Coil Access Panel Left Hood Condensate Pan (Side View) Screw Side Alternate Standard 19-1/16" 19-1/16" Drain Plug Bottom Drain (483mm) (483mm) Side Drain (Factory-Installed) Fig. 15 — Condensate Drain Pan (Side View) 33-3/8" 33-3/8" To use the alternate bottom drain connection, remove the red (848mm) (848mm) drain plug from the bottom connection (use a...
  • Page 16: Field Power Supply

    NOTE: Check all factory and field electrical connections for tight- ness. Field-supplied wiring shall conform with the limitations of WARNING minimum 63°F (33°C) rise. FIELD POWER SUPPLY FIRE HAZARD Failure to follow this warning could result in personal If equipped with optional powered convenience outlet: the injury, death, or property damage.
  • Page 17: Units Without Factory-Installed Non-Fused Disconnect

    Operation on im- which is located below the convenience outlet. proper line voltage or excessive phase imbalance constitutes abuse and may cause damage to electrical components. Such operation would invalidate any applicable Bryant warranty.
  • Page 18: All Units

    leads can be connected at the line-side terminals on the unit- mounted non-fused disconnect; this will provide service power to the unit when the unit disconnect switch is open. Other con- nection methods will result in the convenience outlet circuit being de-energized when the unit disconnect switch is open.
  • Page 19: Units Without Thru-Base Connections

    Building Manage- ment System. THERMOSTAT Select a Bryant-approved accessory thermostat. When electric heat is installed in the 559K unit, the thermostat must be capa- ble of energizing the G terminal (to energize the Indoor Fan Contactor) whenever there is a space call for heat (energizing the W1 terminal).
  • Page 20: Unit Without Thru-Base Connection Kit

    75 ft (15 to 23 m), use no. 16 AWG insulated wire [35°C Main Optional Single Center Vane Axial (95°F) minimum]. For over 75 ft (23 m), use no. 14 AWG insu- Control Factory-Installed Point Post Indoor Fan lated wire [35°C (95°F) minimum]. All wire sizes larger than Disconnect System no.
  • Page 21: Low-Voltage Control Connections

    PERFECT HUMIDITY CONTROL CONNECTIONS ™ Perfect Humidity – Space RH Controller NOTE: The Perfect Humidity system is a factory installed option. Control Wiring The Perfect Humidity dehumidification system requires a field- supplied and field-installed space relative humidity control device. This device may be a separate humidistat control (contact closes on rise in space RH above control setpoint) or a combination thermostat-humidistat control device with isolated contact set for dehumidification control.
  • Page 22 Programmable Thermostat Unit Control Board Thermostat Connections O/W2/B SRTN Fig. 35 — Typical 559K*08-14 Unit with Perfect Humidity™ Dehumidification System and Programmable Thermostat...
  • Page 23 Fig. 36 — Typical Control Wiring Diagram, Electro-Mechanical with W7220 (559K 08-12 230/460/575-3-60 Unit Shown)
  • Page 24 Fig. 37 — Typical Power Wiring Diagram, for Units with Electro-Mechanical Controllers – 559K 08-12, 230/460-3-60 Units Shown...
  • Page 25 Fig. 38 — Typical Control Wiring Diagram, Electro-Mechanical with W7220 – 559K 14, 230/460/575-3-60 Units Shown...
  • Page 26 Fig. 39 — Typical Power Wiring Diagram, for Units with Electro-Mechanical Controller 559K 14, 230/3/60 Unit Shown...
  • Page 27: Economi$Er® X (Factory Option)

    EconoMi$er ® X (Factory Option) Electrical • Rated Voltage — 20 to 30 Vac RMS, 50/60 Hz The EconoMi$er X system is an expandable economizer con- trol system, which includes a W7220 economizer module (con- • Transformer — 100 va maximum system input troller) with an LCD and keypad (see Fig.
  • Page 28: Economizer Module Wiring Details

    Relative Humidity Table 5 — Economizer Module - Right Hand Terminal 5% to 95% RH non-condensing Blocks ECONOMIZER MODULE WIRING DETAILS LABEL TYPE DESCRIPTION Use Fig. 41 and Tables 4 and 5 to locate the wiring terminals Top Right Terminal Blocks for the Economizer module.
  • Page 29: Co2 Sensor Wiring

    Table 6 — HH57AC081 Sensor Wiring Terminations TERMINAL TYPE DESCRIPTION NUMBER LABEL S-BUS Communications S-BUS S-BUS (Enthalpy Control 2 Line 2 Line 2 Line Sensor Bus) S-BUS Communications S-BUS S-BUS (Enthalpy Control Sensor Bus) Use Fig. 42 and Table 7 to set the DIP switches for the desired use of the sensor.
  • Page 30: Setup And Configuration

    IMPORTANT: Table 8 illustrates the complete hierarchy. IMPORTANT: During setup, the economizer module is Your menu parameters may be different depending on your live at all times. configuration. For example, if you do not have a DCV (CO ) sensor, then The setup process uses a hierarchical menu structure that is none of the DCV parameters appear and only MIN POS easy to use.
  • Page 31 Table 8 — W7220 Menu Structure* PARAMETER PARAMETER MENU PARAMETER DEFAULT RANGE AND NOTES VALUE INCREMENT † FIRST STAGE COOLING DEMAND (Y1–IN) ECONO AVAIL YES/NO YES = economizing available; the system can use outside air for free cooling when required FIRST STAGE COOLING RELAY OUTPUT ECONOMIZING YES/NO...
  • Page 32 Table 8 — W7220 Menu Structure* (cont) PARAMETER PARAMETER MENU PARAMETER DEFAULT RANGE AND NOTES VALUE INCREMENT † MECH COOL ON Displays stage of mechanical cooling that is active. 0, 1, or 2 HEAT STAGES ON Displays the stage of heat pump heating that is active. STATUS SUPPLY FAN SPEED (cont)
  • Page 33 Table 8 — W7220 Menu Structure* (cont) PARAMETER PARAMETER MENU PARAMETER DEFAULT RANGE AND NOTES VALUE INCREMENT † 0°F to 50°F ENERGY RECOVERY VENTILATOR UNIT OUTDOOR AIR ERV OAT SP †† 32°F (–18°C to 10°C); TEMPERATURE SETPOINT increment by 1°F Only displayed when AUX1 O = ERV Exhaust fan set point for single speed units.
  • Page 34 Table 8 — W7220 Menu Structure* (cont) PARAMETER PARAMETER MENU PARAMETER DEFAULT RANGE AND NOTES VALUE INCREMENT † COOLING STAGE 3 DELAY 0 min, 5 min, Delay after stage 2 cool has been active. Turns on second stage of 15 min, then cooling when economizer is first stage and mechanical cooling is STG3 DLY 2.0h...
  • Page 35 Table 8 — W7220 Menu Structure* (cont) PARAMETER PARAMETER MENU PARAMETER DEFAULT RANGE AND NOTES VALUE INCREMENT † DISCHARGE AIR S-BUS SENSOR ERROR DA SYLK T ERR Discharge air sensor has failed or become disconnected - check wiring then replace sensor if the alarm continues. OUTSIDE AIR TEMPERATURE SENSOR ERROR OA SENS T ERR Outdoor air temperature sensor has failed or become disconnected...
  • Page 36: Standard Or Single Speed Fan Operation

    STANDARD OR SINGLE SPEED FAN OPERATION The W (heating mode) is not controlled by the W7220 but it re- quires the status to know where to position the OA damper for FAN TYPE = 1 SPEED is not used on 559K 08-14 units. minimum position for the fan speed.
  • Page 37: 2Sp H/C (2 Speed Heat/Cool) Speed Fan Operation

    2SP H/C (2 SPEED HEAT/COOL) SPEED FAN Refer to Table 11 for ENTH CURVE set point values. OPERATION The W7220 calculates the enthalpy and dew point using the OA temperature and humidity input from the OA enthalpy sen- FAN TYPE = 2SP H/C is not used on 559K 08-14 units sor.
  • Page 38: Checkout

    CHECKOUT To perform a Checkout test: Scroll to the desired test in the Checkout menu using the Inspect all wiring connections at the economizer module’s ter- ▲ and ▼ buttons. minals, and verify compliance with the installation wiring dia- Press the (Enter) button to select the item.
  • Page 39: Smoke Detectors

    Smoke Detectors Additional Application Data Refer to the application data document “Factory Installed Smoke detectors are available as factory-installed options on Smoke Detectors for Small and Medium Rooftop Units 2 to 559K models. Smoke detectors may be specified for supply air 25 Tons”...
  • Page 40: Step 11 - Adjust Factory-Installed Options

    Step 11 — Adjust Factory-Installed Options NOTE: The fan speed set up labels are located on the High Volt- age cover in the Control Box. SMOKE DETECTORS Connect a multimeter to the Vdc terminals on the UCB. Smoke detector(s) will be connected at the Unit Control Board Set the Range Switch to either A, B, or C per the Switch (UCB), at terminals marked “Smoke Shutdown.”...
  • Page 41 ESP in. wg Factory Setting: Calculator 9.0 V 3000 Field Setting: 3250 Record field setting here 3500 3750 4000 Switch Range: 4250 4500 4.1 - 7.5 4750 10.0 6.9 - 8.7 5000 7.7 - 10.0 Field Accessories: Economizer * Overlap in A, B, C switch range designed for maximum field adjustment potential.
  • Page 42 Printed in U.S.A. © 2022 Carrier Cat. No. 04-53559009-01 Edition Date: 4-22 Form No: II559K-8-14-01 Rev. B Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. Replaces:New...
  • Page 43: Preliminary Information

    START-UP CHECKLIST 559K 08-14 SINGLE PACKAGE ROOFTOP ELECTRIC COOLING UNITS (Remove and use for job file) NOTE: To avoid injury to personnel and damage to equipment or property when completing the procedures listed in this start-up checklist, use good judgment, follow safe practices, and adhere to the safety considerations/information as outlined in preceding sec- tions of this Installation Instruction document.
  • Page 44 GENERAL Economizer minimum vent and changeover settings to job requirements (if equipped) (Y/N) _____ Verify smoke detector unit shutdown by utilizing magnet test (Y/N) _____ ™ IV. PERFECT HUMIDITY SYSTEM START-UP STEPS 1. Check UCB (Unit Control Board) for jumper 1, 2, 3 (Jumper 1, 2, 3 must be cut and open) (Y/N) _____ 2.

Table of Contents