Wiring Diagram - Promation Engineering P9-120N4-HR Installation & Operation Manual

High resolution proportional control powered feedback
Table of Contents

Advertisement

Wiring Diagram

P910
FEEDBACK OUT
Actuator Specifi cations
ALTERNATE SIGNAL IN
Torque "lb/Nm
Supply Voltage
SIGNAL IN
Max Inrush Current
Running Current
Motor
Runtime (90°@60Hz)
Runtime (90
@50Hz)
O
Duty Cycle
Motor Starts
Weight
Mechanical Connections
Electrical Entry
Electrical Terminations
Environmental Rating
Manual Override
* CONNECTIONS
OPTIONAL
Control
Actuator Case material
Motor Protection
Ambient Temperature
Operating Range
120VAC 230VAC
Neu
L2
Hot
L1
GND GND
Field wiring and
devices by others
Use For:
P(2-8) 120PN4(7)-HR
Torque Switches (if equipped)
For units equipped with torque switches:
Torque switches provide mechanical
overload protection for both the actuated
device and the geartrain.
These are factory set and are not
adjustable without proper equipment.
Torque switches are set to limit actuator
torque to approximately 105% of the
actuator rated output.
The wiring diagram above shows the
internal wiring connections between
the control board, the torque switches
and the motor. The upper torque switch
controls loading in the CW direction,
while the lower switch controls loading in
the CCW direction.
Voltage Out
Amperage Out +4-20mA
GND(-)
P9
(+) 1-5, 0-5, 0-10vdc
17500"lbs/2000Nm
+4-20mA
120vac
230vac
(-)
5.8A
3.8A
3.3A
2.1A
Split Phase Capacitor
58 sec
WHT18
70 sec
25%, Proportional: Managed (75% maximum)
1200 per hour
145lbs/66kg
ISO5211 F16 Rnd 75mm
NOT OPEN*
(2) 3/4" NPT
OPEN COM*
12-16ga
NEMA 4/4X
OPEN*
15.6" Handwheel
NOT CLOSED*
On/Off -Jog, Proportional
CLOSED COM*
Aluminum Alloy, Powder coated
CLOSED*
230°F/110°C Thermal F* Class
*Totally Enclosed Non-Ventilated Motors
-22°F to +125°F
-30°C to +52°C
L2 Neutral
L1 Hot
GND
Items within dotted line indicates internal components
Actuator ships in fully closed position!
WARNING! Do NOT adjust the
torque switch cam settings.
This will VOID the warranty.
Actuator
Voltage
Wire
Gage
Proportional Control
OTX-100
7
Actuator Specifi cations
6
Torque "lb/Nm
5
Supply Voltage
Max Inrush Current
8 (+15v OUT)
Running Current
6
7
Motor
P10
5
6
Runtime (90°@60Hz/vdc)
22000"lbs/2500Nm
4
5
Runtime (90
@50Hz)
O
120vac
230vac
3
Duty Cycle
4
6.5A
4.0A
Motor Starts
2
3
4.0A
2.3A
Weight
1
2
Mechanical Connections
J1
58 sec
1
Electrical Entry
70 sec
DHC-100
J2
Electrical Terminations
Environmental Rating
Manual Override
Control
Actuator Case Material
12
Motor Protection
AUXILIARY
11
SWITCH
SW4
(STANDARD)
10
Ambient Temperature
Operating Range
9
AUXILIARY
8
SWITCH
SW3
(STANDARD)
7
WHT
6
SW1
5
BLK
4
SW2
J1
3
E2
E1
HEATER
2
1
J3
J2
GND Screw
Wire Sizing Chart
MAX distance between Actuator and Supply (feet)
P9
120VAC
Amps
5.8A
-
16
362
14
553
12
940
10
1404
8
Page 4 of 17 P9/10 HV On/Off Series
P9
17500"lbs/2000Nm
120vac
230vac
5.8A
3.8A
3.3A
2.1A
GRY
Close
POSITION
Split Phase Capacitor
FEEDBACK
ORG
1K ohm
58 sec
BLU
70 sec
WHT
Managed (75% maximum)
BLK
1200 per hour
FACTORY
CONNECTOR
BLU
145lbs/66kg (150lbs/68kg w/ -TS)
J4
ISO5211 F16 Rnd 75mm
RED
(2) 3/4" NPT
12-16ga
NEMA 4/4X
15.6" Handwheel
Proportional
Aluminum Alloy, Powder coated
230°F/110°C Thermal F* Class
*Totally Enclosed Non-Ventilated Motors
-22°F to +125°F
-30°C to +52°C
WHT
THERMAL
SWITCH
M
Capacitor
BLK
AC DRIVE
MOTOR
RED
ALL SWITCHES
SHOWN WITH
ACTUATOR IN
FULL OPEN
POSITION
GRN
Wire sizing data is provided in the table to
assist in the selection of the proper wire size for
ProMation actuators using various wire sizes
over distance.
Please make sure to reference the correct
voltage and do not exceed the indicated length
of the wire run for each model.
230VAC
120VAC
3.8A
6.5A
655
-
1058
323
1618
494
2751
839
4106
1252
P10
22000"lbs/2500Nm
120vac
230vac
6.5A
4.0A
4.0A
2.3A
58 sec
70 sec
P10
230VAC
4.0A
622
1005
1537
2614
3901