Zone interface module

Advertisement

6 Connection wiring
Refer to the wireless zone
monitor
engineers
guide
(TSD143) for full wiring details.
Free to download from www.
emsgroup.co.uk
8 Configuration
The ZIM must be added to the WZM, before adding other wireless devices to
the system.
Refer to the wireless zone monitor
engineers guide (TSD143) for full
programming details.
Free to download from
www.emsgroup.co.uk
Specification
Operating temperature
Storage temperature
Humidity
Supply
CAUTION!
Fitting of an incorrect battery type invalidates the product certification and may
result in poor performance.
Output rating
IP rating
Operating frequency
Output transmitter power
Signalling protocol
Dimensions (W x H x D)
Weight
Location
©2022 EMS Ltd. All rights reserved.
-10 to +55 °C
5 to 30 °C
0 to 95% non-condensing
6x AA alkaline (Panasonic LR6AD Powerline /
Varta 4006 Industrial)
2A at 24 VDC
IP65
868 MHz
0 to 14 dBm (0 to 25 mW)
X
120 x 240 x 60 mm
0.95 kg
Type A: For indoor use
7 Connection wiring
When fitting / replacing batteries; observe correct polarity, using only
specified batteries.
Connect the power jumper across the PIN header.
16
32
64
F-SAFE
LED
ENABLE
INPUT 1I NPUT 2
IP- IP+I P- IP+
Once powered, reassemble the device.
9 LED operation
CLOSED
Input 1
LEDs
FAULT
The device has six indication LEDs. Pressing the LED enable button enables
their illumination for 10 minutes before automatically timing out.
2x input fault: YELLOW LED ON
2x input closed: RED LED ON
2x output: RED LED ON
Regulatory information
Manufacturer
Carrier Manufacturing Poland Sp. z o.o.
Ul. Kolejowa 24. 39-100 Ropczyce, Poland
Year of manufacture
See devices serial number label
Certification
0905
Certification body
CPR DoP
0359-CPR-00436
Approved to
EN54-18:2005. Fire detection and fire alarm systems.
Part 18:Input/output devices.
EN54-25:2008. Incorporating corrigenda September 2010
and March 2012. Fire detection and fire alarm systems.
European Union
EMS declares that this device is in compliance with Directive
Directives
2014/53/EU. The full text of the EU declaration of conformity
is available at the following internet address: www.
emsgroup.co.uk
2012/19/EU (WEEE directive): Products marked with this
symbol cannot be disposed of as unsorted municipal waste
in the European Union. For proper recycling, return this
product to your local supplier upon purchase of equivalent
new equipment, or dispose of it at designated collection
points. For more information see www.recyclethis.info
Dispose of your batteries in an environmentally friendly
manner according to your local regulations.
Page 2 of 2
CLOSED
(pins unlinked)
FAULT
EXPA
3VDCS E
Output 1 LED Output 2 LED
Input 2
LEDs
= FAULT
= ACTIVE
= ACTIVE
14
TSD142-99 Issue 7 21/06/2022 AJM
device
unpowered
device
powered
(both pins
linked)

Advertisement