Samsung AR07CSDAFWKN Service Manual page 64

Multi air conditioner
Table of Contents

Advertisement

Troubleshooting
■ AC***BNLDCH, AJ***BNHDCH
• The installation options of indoor units are set to 020010-120000-200000-300000 by default.
Option No. for an indoor unit : 0AXXXX-1XXXXX-2XXXXX-3XXXXX
Option
SEG1
Explanation
PAGE
Indication
Details
Indication and
Details
0
Option
SEG5
Explanation
Use of central control
Indication
Details
0
Disuse
Indication and
Details
1
Use
Option
SEG9
Explanation
Use of Hot Coil
Indication
Details
0
Disuse
Indication and
1
Use
Details
-
4-22
SEG2
MODE
Indication
Details
2
SEG6
RESERVED
SEG10
Use of auxiliary heater
Controller variables for auxiliary heater
Indication
Details
Indication
0
Disuse
0
1
2
3
4
5
1
Use
6
7
8
9
A
Use
B
2
(Heater
C
time delay)
D
E
SEG3
RESERVED
SEG7
Indication
Details
1
SEG11
Details
Time delay for
Set temperature for
auxiliary heat
auxiliary heat on
on
No temperature offset
No delay
No temperature offset
10 minutes
No temperature offset
20 minutes
2.7°F(1.5°C)
No delay
2.7°F(1.5°C)
10 minutes
2.7°F(1.5°C)
20 minutes
5.4°F(3°C)
No delay
5.4°F(3°C)
10 minutes
5.4°F(3°C)
20 minutes
8.1°F(4.5°C)
No delay
8.1°F(4.5°C)
10 minutes
8.1°F(4.5°C)
20 minutes
10.8°F(6°C)
No delay
10.8°F(6°C)
10 minutes
10.8°F(6°C)
20 minutes
SEG4
Use of external room temperature sensor /
Minimizing fan operation when
1)
thermostat is off
Details
Use of
Indication
external room
Minimizing fan operation
temperature
when thermostat is off
sensor
0
Disuse
1
Use
2
Disuse
Use(Heating)
3
Use
Use(Heating)
4
Disuse
Use(Cooling)
5
Use
Use(Cooling)
6
Disuse
(Cooling/Heating)
7
Use
(Cooling/Heating)
Use (Cooling Ultra low
8
Disuse
Use (Cooling Ultra low
9
Use
Use (Heating/ Cooling
A
Disuse
Ultra low speed))
Use (Heating/ Cooling
B
Use
Ultra low speed)
SEG8
Use of drain pump
Indication
Details
0
Disuse
1
Use
2
Use + 3minute delay
SEG12
RESERVED
Samsung Electronics
Disuse
Disuse
Use
Use
speed)
speed)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents