Daikin VRV RXYQ72-384XAYCA Service Manual page 166

Heat pump 60 hz
Table of Contents

Advertisement

Field Settings for Indoor Unit
1.3.27 External Static Pressure Settings
Make external static pressure setting automatically using automatic airflow adjustment (11 (21)-7),
or manually using external static pressure settings (13 (23)-6).
FXSQ-TA, FXSQ-TB models
1. FXSQ18-48TA, FXSQ18-48TB cannot be set to 30-40 Pa (0.12-0.16 inWG).
2. FXSQ54TA, FXSQ54TB cannot be set to 30-40 Pa (0.12-0.16 inWG) or 150 Pa (0.60 inWG).
FXMQ-PB models
The Second Code No. is set to 02 for FXMQ07/09/12PB, and 07 for FXMQ15/18/24/30/36/48/54PB
at factory setting.
1. FXMQ15/18/24/30/36/48PB cannot be set to 30 Pa (0.12 inWG).
2. FXMQ07/09/12PB cannot be set to 110-200 Pa (0.44-0.80 inWG).
3. FXMQ54PB cannot be set to 30 Pa (0.12 inWG) or 150-200 Pa (0.60-0.80 inWG).
159
Mode No.
First Code No.
13 (23)
6
Mode No.
First Code No.
13 (23)
6
Second Code No.
03
30 Pa (0.12 inWG) (1) (2)
04
40 Pa (0.16 inWG) (1) (2)
05
06
07
08
09
10
11
12
13
14
15
Second Code No.
01
30 Pa (0.12 inWG) (1) (3)
02
03
04
05
06
07
08
09
10
11
12
150 Pa (0.60 inWG) (2) (3)
13
160 Pa (0.64 inWG) (2) (3)
14
180 Pa (0.72 inWG) (2) (3)
15
200 Pa (0.80 inWG) (2) (3)
Part 5 Field Settings and Test Operation
SiUS342004EB
: Factory setting
Contents
50 Pa (0.20 inWG)
60 Pa (0.24 inWG)
70 Pa (0.28 inWG)
80 Pa (0.32 inWG)
90 Pa (0.36 inWG)
100 Pa (0.40 inWG)
110 Pa (0.44 inWG)
120 Pa (0.48 inWG)
130 Pa (0.52 inWG)
140 Pa (0.56 inWG)
150 Pa (0.60 inWG) (2)
: Factory setting
Contents
50 Pa (0.20 inWG)
60 Pa (0.24 inWG)
70 Pa (0.28 inWG)
80 Pa (0.32 inWG)
90 Pa (0.36 inWG)
100 Pa (0.40 inWG)
110 Pa (0.44 inWG) (2)
120 Pa (0.48 inWG) (2)
130 Pa (0.52 inWG) (2)
140 Pa (0.56 inWG) (2)