Daikin VRV RXYQ72-384XAYCA Service Manual page 106

Heat pump 60 hz
Table of Contents

Advertisement

Protection Control
Radiation Fin
Perform the following control of integrated as well as multi units for each compressor.
Temperature
Control
99
Normal control
A
Reduce compressor capacity
Fin temperature standby
Condition
All outdoor units
A
more than 90°C (194°F)
B
less than 87°C (188.6°F)
C
more than 95°C (203°F)
B
C
When occurring 4 times within 60
minutes, the error code L4 is output.
SiUS342004EB
Part 4 Functions and Control